| 2006-06-07 00:00:00 | PROVISO:2001 FBC/BUILDING 4/6 UNITS |
| | |
| | PLEASE REVISE PLANS TO REFLECT THE |
| | IMPLEMENTATION OF THE FOLLOWING |
| | PROVISO'S: |
| | |
| | 1.PLAN SHEET M0.1 THE AHU MOUNTING |
| | DETAIL NOTE 15 STATES "NO COMBUSTIBLES |
| | ALLOWED IN THE MECHANICAL CLOSET" AS |
| | THIS SREVES AS A RETURN AIR PLENUM.THE |
| | DOOR SCHEDULE ON PLAN A-4.1.1 INDICATES |
| | A WOOD LOUVERED DOOR.PLEASE VERIGY |
| | WITH THE DOOR MANUFACTURE THAT THIS |
| | MEETS THE REQUIREMENT OF 25 FLAME/50 |
| | SMOKE INDEX AS SPECIFIED IN 2001 FMC |
| | 602.2.1. |
| | |
| | 2.OUTSIDE AIR CALCULATIONS INDICATED |
| | ON M0.1 ARE BASED ON INFILTRATION RATES. |
| | THE INFILTRATION RATES ARE THE "MAXIMUM" |
| | ALLOWED BY CODE & MAY NOT BE A |
| | "TRUE/ACTUAL" RATE.PLEASE PROVIDE O.A. |
| | CALCS IN ACCORDANCE WITH 2001 FMC 402.2, |
| | 402.2.1 OR TABLE 403.3.PLEASE NOTE, |
| | PLAN SHEET M2 INDICATES A 6" O.A. DUCT, |
| | IF THIS IS NOT UTILIZED PLEASE REMOVE |
| | FROM THE PLANS. |
| | |
| | 3.SPECIFIC DRYERS ARE TO BE INSTALLED |
| | BY FINAL INSPECTION. |
| | |
| | 4.RETURN AIR INDICATED ON THE FIRST |
| | FLOOR (M1) BETWEEN THE GARAGE AND THE |
| | FOYER DOOR IS NOT REQUIRED PER2001 FMC |
| | 601.4 EXCEPTION #3, AS THIS IS NOT A |
| | HABITABLE SPACE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |