| Plan Review Notes For Permit 05090955 |
| Permit Number |
05090955 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-14 00:00:00 | ******* NOTES REDINED,******* | | | ** PLANS ARE TO BE REVISED. ***** | | | | | | ** PLEASE SEE SOME COMMENTS FROM | | | PREVIOUS REVIEW AND SOME NEW COMMENTS | | | DUE TO CHANGES IN PLANS. | | | | | | 1) NOTE: PLEASE SEE MIN OCP FOR AHU | | | HEAT, SHALL BE SIZED PER 424.3B , 125% | | | MIN. | | | PLEASE SEE 40A OCP NOW SHOWN???? | | | | | | 2) NOTE: PLEASE SEE NO SEC'S ARE SHOWN | | | ON RISER FROM FPL TO NEW 1000A SERVICE?? | | | SEC'S ARE SHOWN INAIC | | | CALCS.240.4,310.16, 215.5 ETC. | | | | | | 3) NOTE: PLEASE SEE MIN GEC SHALL BE | | | SIZED PER 250.66. A #4 IS STILL SHOWN, | | | THIS WAS FROM PREVIOUS PLANS AND NEEDS | | | TO BE ADJUST WHEN SEC'S ARE SIZED. | | | PLEASE SEE 3/0 MIN. | | | | | | IF PLANS COME BACK FOR ANY OTHER | | | COMMENTS, REVISE AT THAT TIME. IF PLANS | | | PASS ALL TRADES THIS REVIEW, REVISE | | | BEFORE ANY ROUGH SLAB INSPECTION. | | | INCLUDING SLAB. |
|