Plan Review Notes
Plan Review Notes For Permit 05090954
Permit Number 05090954
Review Stop G
Sequence Number 1
Notes
Date Text
2005-11-14 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - ALL CUT SECTIONS FOR
 NEW SYSTEM SHALL BE SHOWN ON RISER
 DIAGRAM.
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 3. SHOW LOCATION OF REGULATORS, AND
 SUBMIT MANUF. SPECIFICATION SHEETS FOR
 REGULATORS.
 4. MANUF. SHTTE INDICATES 54 CU/FT HR,
 BUT GAS RISER DIAGRAM INDICATES45K.
 PLEASE CLARIFY.
 5. GAS CHARTS FROM FBC-2001 TO BE USED.
 PLEASE INDICATE WHICH CHARTS FROM
 FBC-2001 FUEL GAS SHALL ARE USED FOR THE
 DESIGN. SECTION 402.
 6. ALL INFORMATION, DRAWINGS
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1.
  