| Plan Review Notes For Permit 05090954 |
| Permit Number |
05090954 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. - ALL CUT SECTIONS FOR | | | NEW SYSTEM SHALL BE SHOWN ON RISER | | | DIAGRAM. | | | 2. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | 3. SHOW LOCATION OF REGULATORS, AND | | | SUBMIT MANUF. SPECIFICATION SHEETS FOR | | | REGULATORS. | | | 4. MANUF. SHTTE INDICATES 54 CU/FT HR, | | | BUT GAS RISER DIAGRAM INDICATES45K. | | | PLEASE CLARIFY. | | | 5. GAS CHARTS FROM FBC-2001 TO BE USED. | | | PLEASE INDICATE WHICH CHARTS FROM | | | FBC-2001 FUEL GAS SHALL ARE USED FOR THE | | | DESIGN. SECTION 402. | | | 6. ALL INFORMATION, DRAWINGS | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. | | | SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|