| Plan Review Notes For Permit 05090951 |
| Permit Number |
05090951 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-01-04 00:00:00 | | | | DENIED | | | ~~~~~~ | | | THE TRANSFER SWITCH SUBMITTED FOR | | | REVIEW IS NOT SERVICE RATED ACCORDING TO | | | THE SPECIFICATIONS SUBMITTED.ON THE LOAD | | | SIDE OF THE MAIN PANEL IT IS NOT | | | REQUIRED TO BE SERVICE RATED, BUT AS A | | | DISCONNECTING MEANS FOR THE GENERATOR IT | | | MUST BE PER 225.36. A RATED DISCONNECT | | | MOUNTED PER 225.32 (ON THE BUILDING), | | | BETWEEN THE GENERATOR AND ATS, WOULD | | | SATISFY THIS REQUIREMENT. | | | | | | RESUBMIT SHOWING THIS DISCONNECT ON THE | | | RISER. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|