Plan Review Notes
Plan Review Notes For Permit 05090944
Permit Number 05090944
Review Stop E
Sequence Number 2
Notes
Date Text
2005-11-29 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} IN REFERENCE TO NOTE #7 ON SHEET E-1,
 THE EQUIPMENT GROUNDING CONDUCTOR RAN
 WITH THE NEUTRAL FROM THE METER TO THE
 PANEL, CREATES A PARALLEL PATH AND NEEDS
 TO BE REMOVED, OR ISOLATE THE NEUTRAL
 FROM THE GROUND IN THE PANEL. SEE 250.6.
  
 2} THE SMALL APPLIANCE CIRCUITS WERE
 OMITTED FROM THE PANEL SCHEDULE. REF.
 210.52(B).
  
 3} PLEASE INDICATE THE SIZE OF THE
 GROUNDING ELECTRODE CONDUCTOR ON THE
 RISER DIAGRAM. 250.66 FOR SIZE.
  
 4} THE FAMILY ROOM AND BEDROOM
 RECEPTACLES DO NOT MEET SPACING PER
 210.52(A)(1)&(2), SEE REVIEWED SET.
  
 5} THE PENINSULAR NEEDS A RECEPTACLE PER
 210.52(C)(3).
  
 6} THE COUNTERTOP RECEPTACLE SPACING
 MUST COMPLY WITH 210.52(C)(3).
  
 7} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT THEIR NAME AS WELL
 AS SIGNING THE PLAN. 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  