| 2005-11-29 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} IN REFERENCE TO NOTE #7 ON SHEET E-1, | | | THE EQUIPMENT GROUNDING CONDUCTOR RAN | | | WITH THE NEUTRAL FROM THE METER TO THE | | | PANEL, CREATES A PARALLEL PATH AND NEEDS | | | TO BE REMOVED, OR ISOLATE THE NEUTRAL | | | FROM THE GROUND IN THE PANEL. SEE 250.6. | | | | | | 2} THE SMALL APPLIANCE CIRCUITS WERE | | | OMITTED FROM THE PANEL SCHEDULE. REF. | | | 210.52(B). | | | | | | 3} PLEASE INDICATE THE SIZE OF THE | | | GROUNDING ELECTRODE CONDUCTOR ON THE | | | RISER DIAGRAM. 250.66 FOR SIZE. | | | | | | 4} THE FAMILY ROOM AND BEDROOM | | | RECEPTACLES DO NOT MEET SPACING PER | | | 210.52(A)(1)&(2), SEE REVIEWED SET. | | | | | | 5} THE PENINSULAR NEEDS A RECEPTACLE PER | | | 210.52(C)(3). | | | | | | 6} THE COUNTERTOP RECEPTACLE SPACING | | | MUST COMPLY WITH 210.52(C)(3). | | | | | | 7} THE PERSON TAKING RESPONSIBILITY FOR | | | THE PLAN MUST PRINT THEIR NAME AS WELL | | | AS SIGNING THE PLAN. 104.2.1 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|