| 2005-11-30 00:00:00 | DENIED |
| | |
| | |
| | 5.PROJECT IMPROVEMENT IS CONSIDERED A |
| | SUBSTANTIAL IMPROVEMENT SEC 94-611 WPB |
| | DEFINITIONS. |
| | SINCE EXISTING BUILDING IS IN A FLOOD |
| | ZONE THE EXISTING STRUCTURE SHALL BE |
| | BROUGHT UP TO 6 INCHES ABOVE THE BASE |
| | ELEVATION OF 7 FEET. OR A FINISH FLOOR |
| | HEIGHT OF 7FT. 6INCHES. |
| | NOTE: A/C PADS SHALL BE AT THE 7'6" |
| | FINISH FLOOR HEIGHT. |
| | |
| | 7.SHOW METHOD OF ATTIC VENTILATION ON |
| | ROOM ADDITION.FBC 2309.7.1 |
| | |
| | 8.ALL PRODUCT APPROVALS WITH QUALITY |
| | ASSURANCE SHALL HAVE THE FOLLOWING STATE |
| | PRODUCT APPROVALS ATTACHED. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | **CONSTRUCTION GLASS INDUSTRIES MISSING |
| | STATE PRODUCT APPROVAL. |
| | *** SHOW STRAPS AND TIE-DOWNS USED ON |
| | STRUCTURAL PAGE AND SUBMIT PRODUCT |
| | APPROVALS FOR THEM. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |