| Plan Review Notes For Permit 05090944 |
| Permit Number |
05090944 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-29 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL ADDED LOADS,ALL EXISTING | | | LOADS AND THE EXISTING OR PROPOSED | | | SERVICE SPECIFICATIONS PER 215.15. | | | | | | 2} PLEASE NOTE THAT THE SMOKE DETECTOR | | | IN THE CLOSET OFF THE MASTER BATH MUST | | | BE A MINIMUM OF 3' FROM THE BATHROOM | | | DOOR. SEE NFPA-72 8-1.4.1.2. | | | | | | 3} IF THE "DESIGNER" WHO IS TAKING | | | RESPONSIBIITY FOR THE PLANS IS LICENSED | | | UNDER CH. 481 FS, PLEASE COMPLY WITH THE | | | FAC WITH REGARD TO SEAL AND CA NUMBER. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|