| Plan Review Notes For Permit 05090939 |
| Permit Number |
05090939 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-28 00:00:00 | DENIED | | | | | | 1) CONCRETE WALL DOES NOT HAVE ADEQUATE | | | VERTICAL REINFORCEMENT TO RESIST 140 MPH | | | WINDLOADS. SUBMIT CALCULATIONS.FBC | | | 104.2.1.2 | | | | | | 2) A CONTINOUS TIE BEAM OR BOND BEAM | | | WITH CONTINOUS HORIZONTAL REINFORCEMENT | | | IS REQUIRED. FBC 2101. | | | | | | 3) PROVIDE DETAIL OF THE TIE BEAM AT THE | | | CHANGE OF ELEVATION FROM 6' TO 4'. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|