| Date |
Text |
| 2005-10-08 00:00:00 | ******** UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE TWO INDIVIDUAL TH |
| | UNITS ARE BEING CONVERTED INTO ONE. |
| | PLEASE SEE ELECTRICAL SERVICE SHALL |
| | CONTAIN ONLY ONE MAIN AND ONE SERVICE. |
| | PLEASE SUBMIT RISER DIAGRAM WITH REVISED |
| | ELECTRICAL FOR NEW WORK TO BE DONE. |
| | 230.2. |
| | |
| | |
| | 2)NOTE: PLEASE SEE RECEPTS AT KITCHEN |
| | COUNTERSPACE, BATH RM AND GARAGE ARE ALL |
| | TO BE GFI / GFI PROTECTED. |
| | 210.8A6,210.8A1, 210.8A2 |
| | |
| | 3)NOTE: PLEASE PROVIDE A REVISED PANEL |
| | SCHEDULE FOR NEW ELECTRICAL WORK. |
| | WASHER, DRYER, DEDICATED BRANCH CIRCUITS |
| | REQUIRED UNDER 210.52D, 210.52B1, |
| | 210.11C1,C3 ETC. |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE PROVIDE ALL ROOM/AREA |
| | DESIGNATIONS ON PLANS. |
| | PLEASE ALSO IDENTIFY FLRS. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE SEE WATER HEATER SHOWN |
| | MAY NOT BE LOCATED IN A CLOSET |
| | CONTAINING COMBUSTIBLES. 422.17 |
| | |
| | 6)NOTE: PLANS SHALL CONTAIN THE PRINTED |
| | NAME AND THE SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR PLANS/DESIGN. |
| | FBC 104.2.1, CITY WIDE ADMINISTRATIVE |
| | CODE. |
| | |
| | 7)NOTE: PLEASE SEE SWITCHES CONTROLING |
| | LITGHTING ETC FROM TWO OR MORE LOCATIONS |
| | ARE 3-WAY SWITCHES. PLEASE SEE MISPRINT |
| | ON PLANS WHICH INDICATE A SWITCH WITH 2? |
| | AND LISTED ON SYMBOL SCHEDULE AS 2-WAY? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |