Date Text
2006-01-23 00:00:00PERMIT EXPEDITOR CAME IN AND CORRECTED
 SETS.
 SEE THE FOLLOWING FOR REDLINED ITEMS.
  
  
  
  
  
 1)NOTE: PLEASE SEE NOC HAS SINCE EXPIRED
 PER FS 713.13(2).
 IF WORK HAS NOT COMMENCED WITHIN 90 DAYS
 OF RECORDING OF SAID NOC. THE NOC SHALL
 BECOME VOID AND WILL BE REQUIRED TO BE
 RE-RECORDED BEFORE PICKING UP OF PERMIT.
  
  
 ** REDLINED,
  
 2002NEC210.8B3 AS SOME KITCHEN AREA
 RECEPTS DO NOT APPEAR TO BE NOTED OR
 CONTAIN GFI RECEPTS/PROTECTION AS
 REQUIRED.
 PLEASE SEE AREAS CONTAING EQUIPMENT FOR
 KITCHEN, FOOD PREP ETC SHALL BE
 CONSIDERED PART OF THE KITCHEN AREA.
  
 ** REDLINED ,
 250.6,250.24 FOR THE "BOND" SHOWN FROM
 METER CT CAN.
 THE GROUNDING OF ELECTRICAL SYSTEMS,
 CIRCUIT CONDUCTORS, SURGE ARRESTERS, AND
 CONDUCTIVE NON?CURRENT-CARRYING
 MATERIALS AND EQUIPMENT SHALL BE
 INSTALLED AND ARRANGED IN A MANNER THAT
 WILL PREVENT OBJECTIONABLE CURRENT OVER
 THE GROUNDING CONDUCTORS OR GROUNDING
 PATHS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  