| Plan Review Notes For Permit 05090897 |
| Permit Number |
05090897 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-01-23 00:00:00 | PERMIT EXPEDITOR CAME IN AND CORRECTED | | | SETS. | | | SEE THE FOLLOWING FOR REDLINED ITEMS. | | | | | | | | | | | | | | | | | | 1)NOTE: PLEASE SEE NOC HAS SINCE EXPIRED | | | PER FS 713.13(2). | | | IF WORK HAS NOT COMMENCED WITHIN 90 DAYS | | | OF RECORDING OF SAID NOC. THE NOC SHALL | | | BECOME VOID AND WILL BE REQUIRED TO BE | | | RE-RECORDED BEFORE PICKING UP OF PERMIT. | | | | | | | | | ** REDLINED, | | | | | | 2002NEC210.8B3 AS SOME KITCHEN AREA | | | RECEPTS DO NOT APPEAR TO BE NOTED OR | | | CONTAIN GFI RECEPTS/PROTECTION AS | | | REQUIRED. | | | PLEASE SEE AREAS CONTAING EQUIPMENT FOR | | | KITCHEN, FOOD PREP ETC SHALL BE | | | CONSIDERED PART OF THE KITCHEN AREA. | | | | | | ** REDLINED , | | | 250.6,250.24 FOR THE "BOND" SHOWN FROM | | | METER CT CAN. | | | THE GROUNDING OF ELECTRICAL SYSTEMS, | | | CIRCUIT CONDUCTORS, SURGE ARRESTERS, AND | | | CONDUCTIVE NON?CURRENT-CARRYING | | | MATERIALS AND EQUIPMENT SHALL BE | | | INSTALLED AND ARRANGED IN A MANNER THAT | | | WILL PREVENT OBJECTIONABLE CURRENT OVER | | | THE GROUNDING CONDUCTORS OR GROUNDING | | | PATHS. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | |
|