| Date |
Text |
| 2006-03-20 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)PREVIOUS CORRECTION LISTS HAD |
| | REQUESTED THAT SCOPE OF WORK REGARDING |
| | THE ROOF BE CLARIFIED.NOW SHEET 1 |
| | STATES THAT THE ROOF IS TO BE PAINTED |
| | RATHER THAN REPLACED.S1.2 SPECIFIES |
| | REPLACEMENT OF SHEATHING WHICH IMPLIES |
| | THAT ROOF WORK WILL BE DONE.THIS |
| | COMMENT DOES NOT HAVE TO BE ADDRESSED ON |
| | THE PLAN BUT BE ADVISED THAT PRODUCT |
| | APPROVALS FOR THE METAL ROOF WILL BE |
| | REQUIRED UNDER SEPARATE PERMIT. |
| | |
| | 2.)THE NEW SHEETS T1 AND A9.1 ARE TO |
| | BE SIGNED, SEALED, AND DATED. |
| | FAC61G1-16.STATUTORY REQUIREMENTS |
| | CANNOT BE WAIVED PER BUILDING OFFICIAL. |
| | |
| | 3.)REMOVE THE REDUCED ARCHITECTURAL |
| | SHEETS, EXCEPT FOR THE FOOD SERVICE PLAN |
| | APPROVAL AND ANY OTHER SHEETS WHICH MAY |
| | HAVE APPROVALS FROM OTHER GOVERNMENTAL |
| | ENTITIES. |
| | |
| | 4.)ON ONE OF THE SETS, SOMEONE HAS |
| | CHANGED THE 2001 FBC TO 2003 FBC.THE |
| | OTHER PLAN IS STILL 2001 FBC.THIS |
| | PROJECT COULD BE PERMITTED UNDER EITHER |
| | FBC2001 OR FBC2004.IT WAS REVIEWED |
| | UNDER FBC2001.DECLARE GOVERNING CODE. |
| | CHANGING THE CODE AT THIS POINT WILL |
| | RESULT IN ADDITIONAL DELAYS. |
| | |
| | 5.)PRODUCT APPROVALS HAVE BEEN |
| | REQUESTED TWICE.ONLY WINDOW PRODUCT |
| | APPROVALS WERE PROVIDED.ALSO REQUIRED |
| | ARE PRODUCT APPROVALS FOR SIDING, DOORS, |
| | AND THE METAL ROOF.SEE ALSO COMMENT #1 |
| | ABOVE. |
| | |
| | NEW COMMENTS: |
| | |
| | 6.)A1.1 DECLARES THIS BUILDING AS TYPE |
| | II CONSTRUCTION, WHICH REQUIRES THAT ALL |
| | STRUCTURAL ELEMENTS ARE NONCOMBUSTIBLE |
| | AND MEET THE FIRE RESISTANCE |
| | REQUIREMENTS OF FBC TABLE 600, FBC604. |
| | THIS IS IN CONFLICT WITH THE STRUCTURAL |
| | DETAILS. IN ADDITION TO REQUIRING |
| | NONCOMBUSTIBLE CONSTRUCTION AND FIRE |
| | RATING IN COMPLIANCE WITH TABLE 600, |
| | COMBUSTIBLES IN CONCEALED SPACES ARE NOT |
| | ALLOWED AND THIS MUST BE NOTED ON THE |
| | PLAN IF THE BUILDING IS TO BE A TYPE II. |
| | NOTE THAT THE NEW STRUCTURAL SHOW |
| | EXTERIOR COMBUSTIBLE NONBEARING WALLS AS |
| | WELL AS AN EXISTING COMBUSTIBLE ROOF. |
| | ADDRESS. |
| | |
| | 7.)WHEN RESUBMITTING, INCLUDE A |
| | RESPONSE LETTER INDICATING HOW EACH ITEM |
| | WAS ADDRESSED. |