Plan Review Notes
Plan Review Notes For Permit 05090897
Permit Number 05090897
Review Stop P
Sequence Number 2
Notes
Date Text
2006-01-28 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 PREVIEW.
 PLUMBINGDENIED
 PREVIOUS COMMENTS DATED 11-26-05 NOT
 ADDRESSED.
 PLAN REVIEW COMMENTS SHALL BE RESPONDED
 TO BY THE DESIGN PROFESSIONALS. REFERING
 TO EACH OTHER OR CONTRACTOR, IS NOT
 HELPFUL IN EXPEDITING YOUR PERMIT.
  
 2. APPLICATION INDICATES "REPAIR STORM
 DAMAGE", BUT NEW FLOOR PLAN INDICATES
 ALTERATION OF SPACE. PLEASE DESCRIBE
 PROJECT IN DETAIL AS REQUIRED ON
 APPLICATION FOR PERMIT.
  
 5. PLANS SHALL BE ROUTED TO STATE OF
 FLORIDA DBPR HOTEL AND RESTURANT DIV.
 FOR REVIEW PRIOR TO RESUBMITTING TO CITY
 WPB FOR REVIEW.
 MINIMUM 2 COPIES STAMPED
 BY DBPR WITH 2 PAGE "WORKSHEETS"
 ATTACHED TO EACH SET OF PLANS SUBMITTED
 FOR REVIEW. SECTION 101.4.7. CONTACT
 NUMBER FOR DBPR IS (850) 487-1395
  
 9. SHT P1 CONDENSATE SHALL NOT DRAIN TO
 GUTTER, DOWN SPOUTS
 CONDENSATE SHALL DRAIN
 SEPARATELY OUT OF THE BUILDING AND SHALL
 TERMINATE TO A STORM CATCH BASIN,
 PLANTED AREA OR A DRYWELL. IF CONNECTED
 TO A CATCH BASIN, A RELIEF VENT IS
 REQUIRED AS THE CONDENSATE EXITS THE
 BUILDING. CITY CODE 90-125(B)(5).
  
 12. SHT P1 WATER FILTER SHALL COMPLY
 WITH NSF 42. SUBMIT MANUF. SPECIFICATION
 SHOWING COMPLIANCE. SECTION 611.1
  
 16.SEPERATE GAS STOP FOR GAS.
 END OF COMMNENTS, QUESTIONS 561-805-6692