| 2006-01-28 00:00:00 | PAUL SCHMITZ |
| | FBC2001 FUEL GAS CODEPLAN REVIEW |
| | FBC 2001 PLUMBING CODEPLAN REVIEW |
| | FBC 2001 FL ACESSIBILITY CODE PLAN |
| | PREVIEW. |
| | PLUMBINGDENIED |
| | PREVIOUS COMMENTS DATED 11-26-05 NOT |
| | ADDRESSED. |
| | PLAN REVIEW COMMENTS SHALL BE RESPONDED |
| | TO BY THE DESIGN PROFESSIONALS. REFERING |
| | TO EACH OTHER OR CONTRACTOR, IS NOT |
| | HELPFUL IN EXPEDITING YOUR PERMIT. |
| | |
| | 2. APPLICATION INDICATES "REPAIR STORM |
| | DAMAGE", BUT NEW FLOOR PLAN INDICATES |
| | ALTERATION OF SPACE. PLEASE DESCRIBE |
| | PROJECT IN DETAIL AS REQUIRED ON |
| | APPLICATION FOR PERMIT. |
| | |
| | 5. PLANS SHALL BE ROUTED TO STATE OF |
| | FLORIDA DBPR HOTEL AND RESTURANT DIV. |
| | FOR REVIEW PRIOR TO RESUBMITTING TO CITY |
| | WPB FOR REVIEW. |
| | MINIMUM 2 COPIES STAMPED |
| | BY DBPR WITH 2 PAGE "WORKSHEETS" |
| | ATTACHED TO EACH SET OF PLANS SUBMITTED |
| | FOR REVIEW. SECTION 101.4.7. CONTACT |
| | NUMBER FOR DBPR IS (850) 487-1395 |
| | |
| | 9. SHT P1 CONDENSATE SHALL NOT DRAIN TO |
| | GUTTER, DOWN SPOUTS |
| | CONDENSATE SHALL DRAIN |
| | SEPARATELY OUT OF THE BUILDING AND SHALL |
| | TERMINATE TO A STORM CATCH BASIN, |
| | PLANTED AREA OR A DRYWELL. IF CONNECTED |
| | TO A CATCH BASIN, A RELIEF VENT IS |
| | REQUIRED AS THE CONDENSATE EXITS THE |
| | BUILDING. CITY CODE 90-125(B)(5). |
| | |
| | 12. SHT P1 WATER FILTER SHALL COMPLY |
| | WITH NSF 42. SUBMIT MANUF. SPECIFICATION |
| | SHOWING COMPLIANCE. SECTION 611.1 |
| | |
| | 16.SEPERATE GAS STOP FOR GAS. |
| | END OF COMMNENTS, QUESTIONS 561-805-6692 |