Plan Review Notes
Plan Review Notes For Permit 05090897
Permit Number 05090897
Review Stop E
Sequence Number 2
Notes
Date Text
2006-01-20 00:00:00****** NOTES,
 PLANS TO REMAIN IN "F" STATUS UNTIL NOTE
 #1 BELOW IS ADDRESSED.
  
  
 1)NOTE: AS REQUESTED ON PREVIOUS REVIEW;
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO THE COMPLETE SETS FOR REVIEW AND
 STAMPING. ONLY ONE COPY OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE ONLY .
 **THIS WAS NOT DONE AND A REPRESENTIVE
 FOR PROJECT SHOULD SET UP A TIME WITH
 PLAN REVIEW STAFF TO COME INTO OFFICE TO
 REMOVE SHEETS AND MAKE TWO CLEAN SETS.
  
 2)NOTE: PLEASE SEE NOC HAS SINCE EXPIRED
 PER FS 713.13(2).
 IF WORK HAS NOT COMMENCED WITHIN 90 DAYS
 OF RECORDING OF SAID NOC. THE NOC SHALL
 BECOME VOID AND WILL BE REQUIRED TO BE
 RE-RECORDED BEFORE PICKING UP OF PERMIT.
  
  
 ** REDLINED,
  
 2002NEC210.8B3 AS SOME KITCHEN AREA
 RECEPTS DO NOT APPEAR TO BE NOTED OR
 CONTAIN GFI RECEPTS/PROTECTION AS
 REQUIRED.
 PLEASE SEE AREAS CONTAING EQUIPMENT FOR
 KITCHEN, FOOD PREP ETC SHALL BE
 CONSIDERED PART OF THE KITCHEN AREA.
  
 ** REDLINED ,
 250.6,250.24 FOR THE "BOND" SHOWN FROM
 METER CT CAN.
 THE GROUNDING OF ELECTRICAL SYSTEMS,
 CIRCUIT CONDUCTORS, SURGE ARRESTERS, AND
 CONDUCTIVE NON?CURRENT-CARRYING
 MATERIALS AND EQUIPMENT SHALL BE
 INSTALLED AND ARRANGED IN A MANNER THAT
 WILL PREVENT OBJECTIONABLE CURRENT OVER
 THE GROUNDING CONDUCTORS OR GROUNDING
 PATHS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]