2005-11-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB CITY CODE
  
 1. SHTS T1 THRU A9.1 FIRM LICENSE NUMBER
 IS REQUIRED IN THE TITLE BLOCK OF THE
 ARCHITECT ON EACH SHEET. FAC
 61G1-16.004(2) & FS 481.219 FS 481.2055.
 2. APPLICATION INDICATES "REPAIR STORM
 DAMAGE", BUT NEW FLOOR PLAN INDICATES
 ALTERATION OF SPACE. PLEASE DESCRIBE
 PROJECT IN DETAIL AS REQUIRED ON
 APPLICATION FOR PERMIT.
 3. SHT A1.1 TOILET IN WOMEN'S TOILET
 INDICATEED AS 11-1/8" OFF THE WALL TO
 THE CENTER OF THE W/C. MINIMUM CLEARANCE
 FOR W/C'S IS 15" OFF WALL TO CENTER OF
 FIXTURE. MINIMUM 30" FINISH OPENING
 REQUIRED FOR THIS TOILET. SECTION
 405.3.1. INDICATE ON FLOOR PLAN.
 4. SHT A1.1 TURNING AREA SHALL BE IN THE
 TOILET ROOM, NOT IN THE STALL. PLEASE
 SHOW AREA IN TOILET ROOM. SECTION
 11-4.22.3.
 5. PLANS SHALL BE ROUTED TO STATE OF
 FLORIDA DBPR HOTEL AND RESTURANT DIV.
 FOR REVIEW PRIOR TO RESUBMITTING TO CITY
 WPB FOR REVIEW. MINIMUM 2 COPIES STAMPED
 BY DBPR WITH 2 PAGE "WORKSHEETS"
 ATTACHED TO EACH SET OF PLANS SUBMITTED
 FOR REVIEW. SECTION 101.4.7. CONTACT
 NUMBER FOR DBPR IS (850) 487-1395
 6. SHTS A1.2 & A1.3 EQUIPMENT LAYOUT
 PLAN DOES NOT REFLECT THE EQUIPMENT
 SCHEDULE. AE #53, AE #410, & AE #416 NOT
 FOUND ON LAYOUT PLAN. AE #426 FOUND ON
 FLOOR PLAN DOES NOT INDICATE WATER
 SUPPLY OR DRAIN ON EQUIPMENT SECHEDULE.
 PLEASE CLARIFY. SECTION 104.2.1.
 7. SHTS A4.1 & A4.2 INDICATES "NEW
 PARAPET SEE DETAIL SHEET S1 FOR DETAILS"
 NO SHT S1 SUBMITTED, NO DETAIL FOUND.
 PLEASE CLARIFY. SECTION 104.2.1.
 8. SHT A8.2 RESTROOM ELEVATIONS. PLEASE
 SHOW THE FOLLOWING INFORMATION:
 A. 11-4.16.3 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 D. 11-4.19.5 FAUCETS
 9. SHT P1 CONDENSATE SHALL NOT DRAIN TO
 SANITARY SYSTEM. CONDENSATE SHALL DRAIN
 SEPARATELY OUT OF THE BUILDING AND SHALL
 TERMINATE TO A STORM CATCH BASIN,
 PLANTED AREA OR A DRYWELL. IF CONNECTED
 TO A CATCH BASIN, A RELIEF VENT IS
 REQUIRED AS THE CONDENSATE EXITS THE
 BUILDING. CITY CODE 90-125(B)(5).
 10. SHT P1 ALL FLOOR DRAINS IN THE
 KITCHEN AND DISHWASH AREAS AND THE MOP
 SINK SHALL DRAIN INTO THE GREASE SYSTEM,
 NOT THE SANT. SYSTEM. - ALSO SHOW THESE
 CHANGES ON THE SANT./GREASE ISOMETRIC
 RISER DIAGRAM.
 11. SHT P1 THE NEW GREASE INTERCEPTORS
 SHALL BE SIZED BY LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE
 CONTACT HER AT (561) 822-2271, OR FAX
 (561) 822-2279, OR E-MAIL
 [email protected]. WASTE ORD. #3434.
 12. SHT P1 WATER FILTER SHALL COMPLY
 WITH NSF 42. SUBMIT MANUF. SPECIFICATION
 SHOWING COMPLIANCE. SECTION 611.1
 13. SHT P2 DETAIL #1 GAS WATER HEATER
 DRAIN LINE SHALL DRAIN TO A FLOOR SINK
 OR HUB DRAIN. FLOOR DRAINS ARE NOT AN
 APPROVED INDIRECT WASTE INTERCEPTOR.
 SECTIONS 802.3 & 802.3.2. INDICATE WHERE
 T & P RELIEF VALVE WILL TERMINATE.
 SECTION 504.7.1
 14. SHT P2 DETAIL #5 GREASE INTERCEPTORS
 LIDS TO BE STAMPED "GREASE" NOT SANT. AS
 INDICATED. - A 2-WAY CLEANOUT IS
 REQUIRED UPSTREAM OF THE ENTERANCE OF
 THE GREASE INTERCEPTORS AS WELL AS AT
 THE EXITS.
 15. SUBMIT A WATER RISER ISOMETRIC
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES,
 AND WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9. WATER HAMMER ARRESTORS
 SHALL BE LOCTED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 16. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - ADDING CUT
 SECTIONS PROVIDED CONFLICTS WITH THE
 DEVELOPED LENGTH SHOWN ON SHT P1. PLEASE
 CLARIFY.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -
 PRESSURE ON SHT P-4 GAS RISER DIAGRAM
 INDICATES 2PSI SYSTEM. PLEASE INDICATE
 LOCATION OF REGULATORS REDUCING PRESSURE
 FROM 2PSI TO 1/2PSI. SUBMIT MANUF.
 SPECIFICATION SHEETS FOR REGULATORS
 SHOWING LISTING FOR REGULATORS, AND
 INDICATE VENTING LINES & MATERIAL IF
 REQUIRED.
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS