| 2005-11-26 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | WPB CITY CODE |
| | |
| | 1. SHTS T1 THRU A9.1 FIRM LICENSE NUMBER |
| | IS REQUIRED IN THE TITLE BLOCK OF THE |
| | ARCHITECT ON EACH SHEET. FAC |
| | 61G1-16.004(2) & FS 481.219 FS 481.2055. |
| | 2. APPLICATION INDICATES "REPAIR STORM |
| | DAMAGE", BUT NEW FLOOR PLAN INDICATES |
| | ALTERATION OF SPACE. PLEASE DESCRIBE |
| | PROJECT IN DETAIL AS REQUIRED ON |
| | APPLICATION FOR PERMIT. |
| | 3. SHT A1.1 TOILET IN WOMEN'S TOILET |
| | INDICATEED AS 11-1/8" OFF THE WALL TO |
| | THE CENTER OF THE W/C. MINIMUM CLEARANCE |
| | FOR W/C'S IS 15" OFF WALL TO CENTER OF |
| | FIXTURE. MINIMUM 30" FINISH OPENING |
| | REQUIRED FOR THIS TOILET. SECTION |
| | 405.3.1. INDICATE ON FLOOR PLAN. |
| | 4. SHT A1.1 TURNING AREA SHALL BE IN THE |
| | TOILET ROOM, NOT IN THE STALL. PLEASE |
| | SHOW AREA IN TOILET ROOM. SECTION |
| | 11-4.22.3. |
| | 5. PLANS SHALL BE ROUTED TO STATE OF |
| | FLORIDA DBPR HOTEL AND RESTURANT DIV. |
| | FOR REVIEW PRIOR TO RESUBMITTING TO CITY |
| | WPB FOR REVIEW. MINIMUM 2 COPIES STAMPED |
| | BY DBPR WITH 2 PAGE "WORKSHEETS" |
| | ATTACHED TO EACH SET OF PLANS SUBMITTED |
| | FOR REVIEW. SECTION 101.4.7. CONTACT |
| | NUMBER FOR DBPR IS (850) 487-1395 |
| | 6. SHTS A1.2 & A1.3 EQUIPMENT LAYOUT |
| | PLAN DOES NOT REFLECT THE EQUIPMENT |
| | SCHEDULE. AE #53, AE #410, & AE #416 NOT |
| | FOUND ON LAYOUT PLAN. AE #426 FOUND ON |
| | FLOOR PLAN DOES NOT INDICATE WATER |
| | SUPPLY OR DRAIN ON EQUIPMENT SECHEDULE. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 7. SHTS A4.1 & A4.2 INDICATES "NEW |
| | PARAPET SEE DETAIL SHEET S1 FOR DETAILS" |
| | NO SHT S1 SUBMITTED, NO DETAIL FOUND. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 8. SHT A8.2 RESTROOM ELEVATIONS. PLEASE |
| | SHOW THE FOLLOWING INFORMATION: |
| | A. 11-4.16.3 HEIGHT |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | D. 11-4.19.5 FAUCETS |
| | 9. SHT P1 CONDENSATE SHALL NOT DRAIN TO |
| | SANITARY SYSTEM. CONDENSATE SHALL DRAIN |
| | SEPARATELY OUT OF THE BUILDING AND SHALL |
| | TERMINATE TO A STORM CATCH BASIN, |
| | PLANTED AREA OR A DRYWELL. IF CONNECTED |
| | TO A CATCH BASIN, A RELIEF VENT IS |
| | REQUIRED AS THE CONDENSATE EXITS THE |
| | BUILDING. CITY CODE 90-125(B)(5). |
| | 10. SHT P1 ALL FLOOR DRAINS IN THE |
| | KITCHEN AND DISHWASH AREAS AND THE MOP |
| | SINK SHALL DRAIN INTO THE GREASE SYSTEM, |
| | NOT THE SANT. SYSTEM. - ALSO SHOW THESE |
| | CHANGES ON THE SANT./GREASE ISOMETRIC |
| | RISER DIAGRAM. |
| | 11. SHT P1 THE NEW GREASE INTERCEPTORS |
| | SHALL BE SIZED BY LYNN MASSON, |
| | ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE |
| | CONTACT HER AT (561) 822-2271, OR FAX |
| | (561) 822-2279, OR E-MAIL |
| | [email protected]. WASTE ORD. #3434. |
| | 12. SHT P1 WATER FILTER SHALL COMPLY |
| | WITH NSF 42. SUBMIT MANUF. SPECIFICATION |
| | SHOWING COMPLIANCE. SECTION 611.1 |
| | 13. SHT P2 DETAIL #1 GAS WATER HEATER |
| | DRAIN LINE SHALL DRAIN TO A FLOOR SINK |
| | OR HUB DRAIN. FLOOR DRAINS ARE NOT AN |
| | APPROVED INDIRECT WASTE INTERCEPTOR. |
| | SECTIONS 802.3 & 802.3.2. INDICATE WHERE |
| | T & P RELIEF VALVE WILL TERMINATE. |
| | SECTION 504.7.1 |
| | 14. SHT P2 DETAIL #5 GREASE INTERCEPTORS |
| | LIDS TO BE STAMPED "GREASE" NOT SANT. AS |
| | INDICATED. - A 2-WAY CLEANOUT IS |
| | REQUIRED UPSTREAM OF THE ENTERANCE OF |
| | THE GREASE INTERCEPTORS AS WELL AS AT |
| | THE EXITS. |
| | 15. SUBMIT A WATER RISER ISOMETRIC |
| | DIAGRAM. SHOW ALL PIPE SIZES, VALVES, |
| | AND WATER HAMMER ARRESTORS REQUIRED BY |
| | SECTION 604.9. WATER HAMMER ARRESTORS |
| | SHALL BE LOCTED NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING. |
| | PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | 16. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | A. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | B. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). - ADDING CUT |
| | SECTIONS PROVIDED CONFLICTS WITH THE |
| | DEVELOPED LENGTH SHOWN ON SHT P1. PLEASE |
| | CLARIFY. |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | E. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - |
| | PRESSURE ON SHT P-4 GAS RISER DIAGRAM |
| | INDICATES 2PSI SYSTEM. PLEASE INDICATE |
| | LOCATION OF REGULATORS REDUCING PRESSURE |
| | FROM 2PSI TO 1/2PSI. SUBMIT MANUF. |
| | SPECIFICATION SHEETS FOR REGULATORS |
| | SHOWING LISTING FOR REGULATORS, AND |
| | INDICATE VENTING LINES & MATERIAL IF |
| | REQUIRED. |
| | F. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | REVIEW BY KEN STEVENS |