Plan Review Notes
Plan Review Notes For Permit 05090897
Permit Number 05090897
Review Stop M
Sequence Number 1
Notes
Date Text
2005-11-08 00:00:00PLAN DENIED
 1) PLEASE PROVIDE FRESH AIR CALCULATIONS
 PER TABLE 403.3 FBC(M)
 2) PLEASE REFER TO SECTION 606.2.1
 SUPPLY AIR SYSTEM AND 606.4.1
 SUPERVISION.
 3) ADDITIONAL PERMITS ARE REQUIRED FOR
 HOODS AND WALK IN COOLERS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732