Plan Review Notes
Plan Review Notes For Permit 05090897
Permit Number 05090897
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-10-11 00:00:00******DENIED******
  
 1) AN ADDRESS ON BUILDING IS REQUIRED
 AND SHALL BE A MINIMUM OF 6" IN HEIGHT
 AND CONTRASTING TO BACKGROUND.
  
 2) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
 PLEASE ILLUSTRATE IN TERMS OF CLASS A,B,
 OR C.
  
 3) PLEASE INDICATE THE OCCUPANT LOAD. A
 NEW OCCUPANT LOAD SIGN WILL BE ISSUED
 PRIOR TO OR AT THE TIME OF THE FINAL
 FIRE INSPECTION.
  
 4) PLEASE EXPLAIN THE RELOCATION OF FIRE
 SPRINKLER HEADS ABOVE DRAFT CURTAIN?
  
 5) IN ADDITION TO A "K" TYPE FIRE
 EXTINGUISHER IN THE KITCHEN, 2A-10B,C
 RATED FIRE EXTINGUISHERS ARE REQUIRED.
  
 6) VISUAL/AUDIBLE WARNING DEVICES SHALL
 BE INSTALLED IN THE AREA OF DUCT SMOKE
 DETECTORS.
  
 7) PLANS MENTION HOOD/SUPPRESSION
 SYSTEMS. SEPARATE SHOP DRAWINGS AND
 PERMITS WILL BE REQUIRED.
  
  
 MIKE WENNERGREN, CAPTAIN
 FIRE PLAN REVIEW (561) 805-6722