Plan Review Notes
Plan Review Notes For Permit 05090897
Permit Number 05090897
Review Stop E
Sequence Number 1
Notes
Date Text
2005-10-13 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE INCLUDE RECEPTS REQUIRED
 ABOVE ALL OUTSIDE WINDOWS.210.62
 THESE WILL BE REQUIRED TO DISCOURAGE
 FLOOR RECEPTACLES AND UNSIGHTLY
 EXTENSION CORDS LIKELY TO CAUSE PHYSICAL
 INJURY, RECEPTACLES MUST BE INSTALLED
 DIRECTLY ABOVE A SHOW WINDOW, AND ONE
 RECEPTACLE IS REQUIRED FOR EVERY 12
 LINEAR FT OR ?MAJOR FRACTION THEREOF? (6
 FT OR MORE). SEE 220.3(B)(7) AND
 220.12(A) FOR INFORMATION REGARDING LOAD
 COMPUTATIONS FOR SHOW WINDOWS.
 THESE ARE MAINLY USED FOR SIGNAGE WHICH
 IS TYPICALLY INSTALLED ABOVE WINDOWS.
  
 2)NOTE: PLEASE SEE 600.5 FOR MIN SIGN
 CIRCUIT REQUIRED AT FRONT ENTRANCE
 LOCATION SUBJECT TO PEDESTRIAN TRAFFIC.
  
 3)NOTE: PLEASE SEE AN "EQUIPMENT
 GROUNDING" CONDUCTOR IS BEING SHOWN
 BEFORE THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6,250.24, THE "EQUIPMENT
 GROUNDING CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 4)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM SEEMS TO BE MISSING THE REQUIRED
 CONNECTION TO THE COLD WATER PIPE.
 250.50
  
 5)NOTE: PLEASE SEE "DP" WILL BE REQUIRED
 TO CONTAIN A MCB AS PANEL IS SHOWN AS
 MLO WITH MORE THAN 6 SPACES.
 PLEASE INDICATE THE AS MCB.
 PLEASE KNOW THE MCB WILL ONLY BE
 REQUIRED TO HAVE THE 65,000 AIC RATED
 MAIN AND OTHER BREAKERS IN PANEL MAY BE
 RATED FOR SERIES RATING.
 110.9, 230.70
  
 6)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS
 FOR GFI PROTECTION OF ALL 15/20A 120 V
 RECEPTS.
  
 **PLEASE BE SURE TO SEE FIE REVIEW
 COMMENTS AND ANY POSSIBLE COMMENT SFORM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]