| 2005-10-13 00:00:00 | ****** UNSAT ******* |
| | |
| | 1)NOTE: PLEASE INCLUDE RECEPTS REQUIRED |
| | ABOVE ALL OUTSIDE WINDOWS.210.62 |
| | THESE WILL BE REQUIRED TO DISCOURAGE |
| | FLOOR RECEPTACLES AND UNSIGHTLY |
| | EXTENSION CORDS LIKELY TO CAUSE PHYSICAL |
| | INJURY, RECEPTACLES MUST BE INSTALLED |
| | DIRECTLY ABOVE A SHOW WINDOW, AND ONE |
| | RECEPTACLE IS REQUIRED FOR EVERY 12 |
| | LINEAR FT OR ?MAJOR FRACTION THEREOF? (6 |
| | FT OR MORE). SEE 220.3(B)(7) AND |
| | 220.12(A) FOR INFORMATION REGARDING LOAD |
| | COMPUTATIONS FOR SHOW WINDOWS. |
| | THESE ARE MAINLY USED FOR SIGNAGE WHICH |
| | IS TYPICALLY INSTALLED ABOVE WINDOWS. |
| | |
| | 2)NOTE: PLEASE SEE 600.5 FOR MIN SIGN |
| | CIRCUIT REQUIRED AT FRONT ENTRANCE |
| | LOCATION SUBJECT TO PEDESTRIAN TRAFFIC. |
| | |
| | 3)NOTE: PLEASE SEE AN "EQUIPMENT |
| | GROUNDING" CONDUCTOR IS BEING SHOWN |
| | BEFORE THE FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE 250.6,250.24, THE "EQUIPMENT |
| | GROUNDING CONDUCTOR IS ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 4)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | SYSTEM SEEMS TO BE MISSING THE REQUIRED |
| | CONNECTION TO THE COLD WATER PIPE. |
| | 250.50 |
| | |
| | 5)NOTE: PLEASE SEE "DP" WILL BE REQUIRED |
| | TO CONTAIN A MCB AS PANEL IS SHOWN AS |
| | MLO WITH MORE THAN 6 SPACES. |
| | PLEASE INDICATE THE AS MCB. |
| | PLEASE KNOW THE MCB WILL ONLY BE |
| | REQUIRED TO HAVE THE 65,000 AIC RATED |
| | MAIN AND OTHER BREAKERS IN PANEL MAY BE |
| | RATED FOR SERIES RATING. |
| | 110.9, 230.70 |
| | |
| | 6)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR |
| | KITCHENS IN OTHER THAN DWELLING UNITS |
| | FOR GFI PROTECTION OF ALL 15/20A 120 V |
| | RECEPTS. |
| | |
| | **PLEASE BE SURE TO SEE FIE REVIEW |
| | COMMENTS AND ANY POSSIBLE COMMENT SFORM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMAITON FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-10-11 00:00:00 | IN ELEC FOR REVIEW |