2005-11-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.THE NOC PROVIDED:
 A. IS LACKING THE LEGAL DESCRIPTION,
 FS713.13,
 B. OWNER INFORMATION CONFLICTS WITH OUR
 RECORDS AND THE PERMIT APPLICATION, AND
 C. HAS BEEN SIGNED BY THE CONTRACTOR.
 IS THE CONTRACTOR THE OWNER OF THIS
 PROPERTY? PROVIDE DOCUMENTATION TO SHOW
 THAT THE INDIVIDUAL SIGNING THE NOC IS
 THE OWNER.
  
 2.)THE CA NUMBER FOR VILLA &
 ASSOCIATES IS TO BE ON THE PLAN,
 FAC61G1-16.
  
 3.)THE DESCRIPTION OF WORK ON THE
 PERMIT APPLICATION STATES THAT THIS IS
 HURRICANE REPAIR WORK.THIS IS AN
 ALTERATION.PLEASE REVISE THE
 APPLICATION TO CORRECTLY REFLECT THE
 SCOPE OF WORK.
  
 4.)THE SCOPE OF WORK IS NOT CLEAR.
 A4.1 STATES THAT THE EXISTING STANDING
 SEAM ROOF IS TO BE PAINTED, T1 STATES
 THAT THIS IS A NEW ROOF.
  
 5.)THE DEMO PLAN, A1.0, CONFLICTS WITH
 THE OTHER SHEETS AS TO THE ORIENTATION
 OF THE BUILDING.
  
 6.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FAC9B72.
 STANDING SEAM METAL ROOF
 HARDIBOARD SIDING
 SCREW ANCHORS
  
 7.)THIS IS AN OVER 50% IMPROVEMENT,
 SEE FBC3401.7.2.6.
  
 8.)PROVIDE ROOM DESIGNATIONS ON THE
 FLOOR PLAN, A1.1.
  
 9.)FBC11-4.1(3), WORK AREAS ARE TO BE
 CONSTRUCTED SO THAT INDIVIDUALS WITH
 DISABILITIES CAN APPROACH, ENTER, AND
 EXIT THE AREAS.SHOW COMPLIANCE.SHEET
 A1.2.
  
 10.)THE DOOR TO THE KITCHEN LACKS THE
 CLEARANCE REQUIRED, PULL SIDE, FBC11
 FIGURE 25, FBC11-4.13.6.
  
 11.)THE MENS' BATHROOM DOOR AND THE
 OFFICE DOOR LACK THE CLEARANCE REQUIRED,
 PUSH SIDE, IF THE DOOR HAS A CLOSER AND
 A LATCH, FBC11 FIGURE 25, FBC11-4.13.6.
  
  
 12.)PROVIDE THE DIMENSION ON THE PLAN
 TO SHOW COMPLIANCE WITH FBC11-4.13.7,
 FBC FIGURE 26 TWO HINGED DOORS IN A
 SERIES (BATHROOM).
  
 13.)SHOW ACCESSIBLE SEATING,
 FBC11-5.1.
  
 14.)SHOW ACCESS AISLE, FBC11-5.3.
  
 15.)PROVIDE A DETAIL FOR THE FOOD
 SERVICE AREAS, FBC11-5.5.
  
 16.)IS THERE A TABLEWARE/CONDIMENT
 AREA?PROVIDE A DETAIL, FBC11-5.6.
  
 17.)WHAT IS THE HEIGHT OF THE TABLES
 919, SHEET A1.2?SEE FBC11-5.2.
  
 18.)SHEET A2.1 SHOWS EXIT LIGHTS ON
 THE LEGEND BUT NONE ON THE PLAN.PLEASE
 MAKE CONSISTENT WITH E1.1.
  
 19.)INCLUDE THE DOOR DIMENSION ON THE
 PLAN FOR ALL EGRESS DOORS AND DOORS
 REQUIRED TO BE ACCESSIBLE.
  
 20.)SPECIFY INTERIOR FINISH
 CLASSIFICATION, FBC TABLE 803.3.
  
 21.)WHEN RESUBMITTING, PLEASE REPLACE
 ONLY SHEETS WHICH HAVE CHANGED.TO
 EXPEDITE PLAN REVIEW, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED.