| 2006-05-14 00:00:00 | **** PLANS REDLINED ***** | | | | | | | | | PLANS ARE TO BE REVISED IF PLANS COME | | | BACK WITH ANY COMMENTS FROM OTHER | | | TRADES. | | | | | | ** PLEASE SHOW SEC'S AND CONDUITS ON | | | RISER. | | | (CONDUCTORS ONLY SHOWN ON FAULT CURRENT | | | CALCS. | | | | | | ** PLEASE SEE GEC SHOWN AS #4?? PLEASE | | | SEE 250.66 FOR MIN SIZE. 3/0 AWG. | | | | | | ** PLEASE SEE MIN OCP FOR AHU'S PER | | | 424.3B, 125% MIN. PLANS NOW SHOW 40A | | | OCP??? | | | | | | PLEASE REVISE ALL THE ABOVE BEFORE ROUGH | | | SLAB INSPECTION. | | | |
|