| 2006-06-19 00:00:00 | PROVISO;2001 FBC/BUILDING 3/6 UNITS |
| | RESPONSE TO COMMENTS DATED 2-7-06 |
| | |
| | COMMENT #5:PLAN SHEET M0.1 THE AHU |
| | MOUNTING DETAIL KEYNOTE DETAIL 15 STATES |
| | NO COMBUSTIBLES ALLOWED IN THE RETURN |
| | AIR PLENUM.THE ARCHITECURAL PLANS |
| | (A-4.0.2) THE DOOR SCHEDULE INDICATES |
| | "WOOD LOUVERD DOOR".PLEASE VERIFY WITH |
| | THE DOOR MANUFACTURE THAT THIS DOOR & |
| | FRAME WILL MEET THE 25 FLAME/50 SMOKE |
| | INDEX WHEN TESTED UNDER ASTM 84. |
| | |
| | COMMENT #6:BOOSTER FANS ARE TO BE |
| | REMOVED AND SPECIFIC DRYERS ARE TO BE |
| | INSTALLED.PLEASE NOTE, SPECIFIC DRYERS |
| | ARE TO BE INSTALLED AT FINAL INSPECTION. |
| | |
| | COMMENT #7:PLAN SHEET M0.1. O.A. |
| | CALCULATIONS ARE BASED ON "INFILTRATION |
| | RATES".THESE ARE MAXIMUM RATES ALLOWED |
| | BY THE CODE & MAY NOT BE "ACTUAL/TRUE" |
| | RATES.THE ACTUAL RATE IS NOT KNOWN |
| | UNLESS TESTED.O.A. CALCS ARE IN |
| | ACCORDANCE WITH 2001 FMC 402.2, 402.2.1 |
| | OR TABLE 403.3. PLAN SHEET M2 INDICATESA |
| | 6" O.A. DUCT, PLEASE REMOVE IF THIS IS |
| | NOT GOING TO BE UTILIZED. |
| | |
| | PLEASE REVISE PLANS TO REFLECT THE |
| | IMPLEMENTATION OF PROVISO'S. |
| | |