| 2006-02-07 00:00:00 | DENIED:BUILDING 2 / 2001 FBC |
| | 6 UNITS |
| | 1.PLAN SHEET A-0.0.0 PROJECT |
| | INFORMATION INDICATES TYPE VI, |
| | UNPROTECTED, SPRINKLERED.PLEASE |
| | INDICATE WHICH SYSTEM WILL BE UTILIZED |
| | (13, 13R, 13D?).PLEASE NOTE, |
| | ADDITIONAL COMMENTS MAY BE GENERATED BY |
| | THE RESPONSES GIVEN. |
| | |
| | 2.PLAN SHEET A-4.0.2 KEY NOTES/LEGEND, |
| | ITEM #25 '1HR CHASE REFER TO 11/A-13'. |
| | PLAN SHEET A-13 WAS NOTE SUBMITTED FOR |
| | REVIEW. |
| | |
| | 3.PLEASE CLARIFY FIRE RATING OF THE |
| | WALL SEPARATING THE GARAGE & THE |
| | RESIDENCE, DOES THE RATING CONTINUE TO |
| | THE SLAB OR THE RATED CEILING? |
| | |
| | 4.PLAN SHEET M1 INDICATES SUPPLY & |
| | EXHAUST DUCT PENETRATING A RATED WALL. |
| | DUCT SHALL COMPLY WITH 2001 FMC 607.1.3 |
| | #3 ITEMS 1 THROUGH 4. |
| | |
| | 5.PLAN SHEET M2 INDICATES DRYER |
| | EXHAUST GOING THROUGH THE AHU CLOSET |
| | WHICH APPEARS TO BE A PLENUM.PER 2001 |
| | 601.3 EXHAUST DUCT OR VENTS SHALL NOT |
| | EXTEND INTO OR PASS THROUGH A PLENUM. |
| | |
| | 6.DRYER EXHAUST EXCEEDS 25FT MAXIMUM |
| | WITH THE REDUCTION FOR 90'S.PLAN SHEET |
| | E2.2 INDICATES 'BF' (BOOSTER FAN?). |
| | PLEASE NOTE, INSTALLATION OF DRYER |
| | BOOSTER FANS WILL BE REVIEWED BY THE |
| | BUILDING OFFICIAL UNDER "ALTERNATE |
| | MATERIALS & METHODS" 2001 FMC 103.7.1. |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW.1) A LETTER FROM AN |
| | ENGINEER EMPLOYED BY THE DRYER |
| | MANUFACTURER STATING THE INSTALLATION OF |
| | THE BOOSTER FAN IS ACCEPTABLE AND WILL |
| | NOT VOID THE WARRANTY OF THE DRYER.2) |
| | MEANS OF NOTIFYING THE OWNER SHOULD THE |
| | BOOSTER FAN FAIL.3) MANUFACTURER'S |
| | SUBMITTAL & INSTALLATION DATA FOR THE |
| | BOOSTER FAN.4) PROVIDE ALL PERTINENT |
| | INFORMATION FOR ALL TRADES MECHANICAL, |
| | ELECTRICAL, FIRE, ETC. FOR THE |
| | INSTALLATION OF BOOSTER FANS. |
| | |
| | 7.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS PER TABLE 403.3 OF THE 2001 |
| | FMC. |
| | |
| | 8.PLEASE PROVIVDE DETAIL OF THE AHU |
| | LOCATED IN THE CLOSET.PLEASE NOTE, |
| | MECHANICAL CLOSET SHALL BE CONSTRUCTED |
| | PER 2001 FMC 603.9.NO COMBUSTIBLES |
| | ALLOWED IN THE RETURN AIR PLENUM PER |
| | 2001 FMC 602.2.1. |
| | |
| | 9.PLEASE PROVIDE DETAIL FOR THE |
| | ANCHORING OF THE CONDENSING UNIT PER |
| | 2001 FMC 301.13. |
| | |
| | 10. R/A TRANSFER GRILLES SHALL BE SIZED |
| | IN ACCORDANCE WITH 2001 FMC 601.4 |
| | EXCEPTION 2 & 3, THIS IS A REQUIRED |
| | MINIMUM. |
| | |