2005-09-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} A DISCONNECT PER 225.31 IS REQUIRED
 WHERE THE FEEDER CONDUCTORS ENTER THE
 BUILDING. SEE 225.32 THROUGH 225.37 FOR
 OTHER REQUIREMENTS. ALSO NOTE THAT THIS
 MEANS MUST DISCONNECT BOTH SOURCES
 SIMULTANEOUSLY. SOME OF THESE SWITCHES
 DO NOT.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLANS MUST PRINT AND SIGN NAME TO
 SAME.
  
 3} PLEASE PROVIDA A SITE PLAN INDICATING
 THE LOCATION OF ALL SERVICE AND
 GENERATOR EQUIPMENT PROPOSED LOCATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  