| Plan Review Notes For Permit 05090878 |
| Permit Number |
05090878 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-11-03 08:12:57 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1. SHT P-02 ONLY THE FIXTURES WITHIN THE BATHROOM GROUP | | | SHALL CONNECT TO THE WET-VENTED HORIZONTAL BRANCH | | | DRAIN. SECTION 909.1. THE BREAKROOM SINK SHALL | | | DISCHARGE DOWNSTREAM OF THE BATHROOM FIXTURES. ALSO THE | | | FLOOR PLAN DOES NOT REFLECT THE PIPING SHOWN ON THE | | | SANITARY RISER DIAGRAM WHICH IS CODE COMPLIANT. PLEASE | | | HAVE THE PIPING ON THE FLOOR PLAN REFLECT THE RISER | | | DIAGRAM AND COMPLY WITH SECTION 909.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|