Plan Review Notes
Plan Review Notes For Permit 05090878
Permit Number 05090878
Review Stop B
Sequence Number 4
Notes
Date Text
2006-11-05 11:40:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FOURTH REVIEW.FROM PREVIOUS LISTS,
 NUMBERING REMAINING THE SAME FOR
 CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 NOT ADDRESSED.
  
 3.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 ADDRESSED.PLEASE KEEP THIS IN THE
 PACKAGE.
  
 4-10.)ADDRESSED.
  
 11.)PROVIDE STATE OR LOCAL PRODUCT
 APPROVAL FOR THE FOLLOWING AS PER
 FAC9B72; 4TH REQUEST, ONLY NOAS WERE SUBMITTED.IF A
 FLORIDA STATE PRODUCT APPROVAL IS NOT AVAILABLE, PLEASE
 ADVISE AND A LOCAL PRODUCT APPROVAL WILL BE ISSUED:
  
 MODIFIED ROOF; INDICATE APPROVED ASSEMBLY.TWO
 DIFFERENT NOAS WERE SUBMITTED; ONE FOR JOHN MANVILLE
 OVER WOOD DECK, ONE FOR US INTEC OVER CEMENTITOUS WOOD
 FIBER DECK.NOTE THAT THE STRUCTURALS SPECIFY A WOOD
 DECK, AND THE ARCHITECT SPECIFIES ON A102 JOHN
 MANVILLE.AN APPROVED ASSEMBLY WAS CHOSEN FOR THE US
 INTEC BUT IT DOES NOT APPEAR TO BE THE CORRECT PRODUCT
 FOR THIS APPLICATION.
  
 STANDING SEAM ? CHOOSE APPROVED ASSEMBLY.
  
 OVERHEAD DOOR ? TWO DIFFERENT NOAS WERE SUBMITTED;
 WHICH ARE YOU USING?
  
 METAL DOOR (NO PRODUCT APPROVALS SUBMITTED) MULLIONS
 (NO PRODUCT APPROVALS SUBMITTED)
  
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE NOA
 SUBMITTED.WWW.FLORIDABUILDING.ORG.IF
 A STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, PLEASE ADVISE AND A LOCAL
 PRODUCT APPROVAL WILL BE ISSUED. (NOT ADDRESSED FOR
 OHD, METAL ROOF, FLAT ROOF)
  
 FOR THE MODIFIED PRODUCT APPROVAL,
 SELECT WHICH APPROVED ASSEMBLY YOU WILL
 BE USING.
  
 FOR THE METAL ROOF, SELECT WHICH
 APPROVED ASSEMBLY YOU WILL BE USING.IF
 THE ASSEMBLY REQUIRES ENHANCED
 FASTENING, PROVIDE CALCULATIONS AS
 REQUIRED BY THE PRODUCT APPROVAL.SEE
 PAGE 8.
  
 12.-14.)ADDRESSED.
  
 15.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 16.)SEPARATE PERMIT REQUIRED FOR THE
 WALL AT THE PERIMETER. (NO RESPONSE NECESSARY.)
  
 17-19.)ADDRESSED.
  
 NEW COMMENTS, 4TH REVIEW:
  
 20.)DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FAC61G1-16.003, 004.SHEETS SE1 AND A100
 ARE NOT SEALED.PLEASE CHECK ALL SHEETS.THESE SHEETS
 HAVE BEEN STAMPED BY ZONING.IF YOU SUBMIT NEW SHEETS,
 A NEW ZONING REVIEW WILL BE REQUIRED.
  
 THE FOLLOWING ITEMS MAY BE REDLINE ITEMS IF THE
 ARCHITECT AND ENGINEER AGREE.PLEASE HAVE THEM CONTACT
 ME.
  
 21.)ENTRANCES WHICH ARE NOT ACCESSIBLE SHALL HAVE
 DIRECTIONAL SIGNAGE, FBC11-4.1.3(8)(D).
  
 22.)FRONT DOOR IS TO SWING IN AS PER ARCHITECTURALS.
  
 23.)S101 #4, FIELD NAILING TO BE 6INOC, NOT 8INOC AS
 PER PLAN, FBC* TABLE 2306.1.
  
 24.)PLEASE REVISE PERMIT APPLICATION TO CORRECTLY
 REFLECT SCOPE OF WORK.