| Plan Review Notes For Permit 05090878 |
| Permit Number |
05090878 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-10-25 15:28:19 | 1. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY | | | WITH NFPA 241. | | | 2. PLEASE ENSURE THAT THE ELECTRICAL LIFE SAFETY | | | FIXTURES THAT WERE SHOWN PREVIOUSLY ON PAGE E-02 ARE | | | INSTALLED. | | | 3. INTERIOR FINISH CLASSIFICATIONS ON WALLS AND | | | CEILINGS IN EXIT ACCESS AREAS SHALL BE AT LEAST CLASS A | | | OR B. | | | 4. TACTILE EXIT SIGNAGE REQUIRED AT EXIT DOORS. | | | 5. PAGE A-104 DOES NOT ILLUSTRATE PORTABLE FIRE | | | EXTINGUISHER LOCATIONS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709 |
|