| 2006-10-17 16:19:03 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | THIRD REVIEW.FROM PREVIOUS LISTS, |
| | NUMBERING REMAINING THE SAME FOR |
| | CONSISTENCY |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | NOT ADDRESSED. |
| | |
| | 3.)PROVIDE A SURVEY FOR THIS PROPERTY. |
| | |
| | ADDRESSED.PLEASE KEEP THIS IN THE |
| | PACKAGE. |
| | |
| | 4-7.)ADDRESSED. |
| | |
| | 8.)DECLARE AN OCCUPANT LOAD, FBC10. |
| | |
| | SEE FBC1003.1, CANNOT EXCLUDE "SUPPORTING SPACE" IN |
| | OCCUPANCY CALCULATIONS.SEE ALSO FOOTNOTE 2, FBC202, |
| | DEFINITION OF AREA, GROSS FLOOR. |
| | |
| | |
| | 9.)ADDRESSED. |
| | |
| | 10.)BUILDING AREA IS DIFFERENT ON A104 THAN ON A100 |
| | AND ENERGY CALCS.ALL SHOULD BE THE SAME, SEE COMMENT |
| | 8 ABOVE. |
| | |
| | |
| | 11.)PROVIDE STATE OR LOCAL PRODUCT |
| | APPROVAL FOR THE FOLLOWING AS PER |
| | FAC9B72: |
| | MODIFIED ROOF; INDICATE APPROVED |
| | ASSEMBLY |
| | STANDING SEAM |
| | OVERHEAD DOOR |
| | METAL DOOR (NO PRODUCT APPROVALS SUBMITTED) MULLIONS |
| | (NO PRODUCT APPROVALS SUBMITTED) |
| | |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE NOA |
| | SUBMITTED.WWW.FLORIDABUILDING.ORG.IF |
| | A STATE PRODUCT APPROVAL IS NOT |
| | AVAILABLE, PLEASE ADVISE AND A LOCAL |
| | PRODUCT APPROVAL WILL BE ISSUED. (NOT ADDRESSED FOR |
| | OHD, METAL ROOF, FLAT ROOF) |
| | |
| | FOR THE MODIFIED PRODUCT APPROVAL, |
| | SELECT WHICH APPROVED ASSEMBLY YOU WILL |
| | BE USING. |
| | |
| | FOR THE METAL ROOF, SELECT WHICH |
| | APPROVED ASSEMBLY YOU WILL BE USING.IF |
| | THE ASSEMBLY REQUIRES ENHANCED |
| | FASTENING, PROVIDE CALCULATIONS AS |
| | REQUIRED BY THE PRODUCT APPROVAL.SEE |
| | PAGE 8. |
| | |
| | 12.-14.)ADDRESSED. |
| | |
| | 15.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALCS. |
| | |
| | NEW COMMENTS: |
| | |
| | 16.)SEPARATE PERMIT REQUIRED FOR THE |
| | WALL AT THE PERIMETER. (NO RESPONSE NECESSARY.) |
| | |
| | 17.)ADDRESSED. |
| | |
| | 18.)THE PRESSURES FOR ZONE 3, FLAT |
| | ROOF, APPEAR INCORRECT, S301, FBC TABLE |
| | 1606.2B.PROVIDE CALUCLATIONS. |
| | |
| | 19.)SEE ATTACHED FS552.80(2)(B).A 4X |
| | PLAN REVIEW FEE WILL BE CHARGED IF |
| | COMMENTS ARE NOT ADDRESSED A THIRD TIME. |