Plan Review Notes
Plan Review Notes For Permit 05090878
Permit Number 05090878
Review Stop B
Sequence Number 3
Notes
Date Text
2006-10-17 16:19:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 THIRD REVIEW.FROM PREVIOUS LISTS,
 NUMBERING REMAINING THE SAME FOR
 CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 NOT ADDRESSED.
  
 3.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 ADDRESSED.PLEASE KEEP THIS IN THE
 PACKAGE.
  
 4-7.)ADDRESSED.
  
 8.)DECLARE AN OCCUPANT LOAD, FBC10.
  
 SEE FBC1003.1, CANNOT EXCLUDE "SUPPORTING SPACE" IN
 OCCUPANCY CALCULATIONS.SEE ALSO FOOTNOTE 2, FBC202,
 DEFINITION OF AREA, GROSS FLOOR.
  
  
 9.)ADDRESSED.
  
 10.)BUILDING AREA IS DIFFERENT ON A104 THAN ON A100
 AND ENERGY CALCS.ALL SHOULD BE THE SAME, SEE COMMENT
 8 ABOVE.
  
  
 11.)PROVIDE STATE OR LOCAL PRODUCT
 APPROVAL FOR THE FOLLOWING AS PER
 FAC9B72:
 MODIFIED ROOF; INDICATE APPROVED
 ASSEMBLY
 STANDING SEAM
 OVERHEAD DOOR
 METAL DOOR (NO PRODUCT APPROVALS SUBMITTED) MULLIONS
 (NO PRODUCT APPROVALS SUBMITTED)
  
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE NOA
 SUBMITTED.WWW.FLORIDABUILDING.ORG.IF
 A STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, PLEASE ADVISE AND A LOCAL
 PRODUCT APPROVAL WILL BE ISSUED. (NOT ADDRESSED FOR
 OHD, METAL ROOF, FLAT ROOF)
  
 FOR THE MODIFIED PRODUCT APPROVAL,
 SELECT WHICH APPROVED ASSEMBLY YOU WILL
 BE USING.
  
 FOR THE METAL ROOF, SELECT WHICH
 APPROVED ASSEMBLY YOU WILL BE USING.IF
 THE ASSEMBLY REQUIRES ENHANCED
 FASTENING, PROVIDE CALCULATIONS AS
 REQUIRED BY THE PRODUCT APPROVAL.SEE
 PAGE 8.
  
 12.-14.)ADDRESSED.
  
 15.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 NEW COMMENTS:
  
 16.)SEPARATE PERMIT REQUIRED FOR THE
 WALL AT THE PERIMETER. (NO RESPONSE NECESSARY.)
  
 17.)ADDRESSED.
  
 18.)THE PRESSURES FOR ZONE 3, FLAT
 ROOF, APPEAR INCORRECT, S301, FBC TABLE
 1606.2B.PROVIDE CALUCLATIONS.
  
 19.)SEE ATTACHED FS552.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS ARE NOT ADDRESSED A THIRD TIME.