Plan Review Notes
Plan Review Notes For Permit 05090878
Permit Number 05090878
Review Stop B
Sequence Number 2
Notes
Date Text
2006-04-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 SECOND REVIEW.FROM PREVIOUS LIST,
 NUMBERING REMAINING THE SAME FOR
 CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 NOT ADDRESSED.
  
 3.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 ADDRESSED.PLEASE KEEP THIS IN THE
 PACKAGE.
  
 4.)PROVIDE A SOILS INVESTIGATION
 REPORT FBC1804.2.2.
  
 ONLY ONE WAS PROVIDED.TWO ORIGINALS OF
 ALL DOCUMENTS REQUIRED FOR PERMITTING.
  
 5.)THE ACCESSIBLE PARKING SPACE DOES
 NOT COMPLY WITH CITY OF WEST PALM BEACH
 STANDARDS, SEE ATTACHED.
  
 NOT ADDRESSED.
  
 6-7.)ADDRESSED.
  
 8.)DECLARE AN OCCUPANT LOAD, FBC10.
  
 THE OCCUPANT LOAD CANNOT BE LESS THAN
 TABLE FBC1003.1, FBC1003.1.1.FRACTIONS
 TO BE ROUNDED UP, AS ROUNDING DOWN MAKES
 THIS LESS THAN THE NUMBER IN THE TABLE.
  
 9.)ADDRESSED.
  
 10.)A100 STATES THAT THE BUILDING LOT
 COVERAGE IS 2056.4 SF.A101 STATES THAT
 THE SHOWROOM IS 1182 SF, STORAGE 303 SF.
 ENERGY CALCS STATE THAT THE CONDITIONED
 AREA IS 1682.ADDRESS.
  
 ENERGY CALCS ARE NOT CONSISTENT TO THE
 SF DECLARED ON THE PLAN.
  
 11.)PROVIDE STATE OR LOCAL PRODUCT
 APPROVAL FOR THE FOLLOWING AS PER
 FAC9B72:
 MODIFIED ROOF; INDICATE APPROVED
 ASSEMBLY
 STANDING SEAM
 OVERHEAD DOOR
 FRONT DOOR
 METAL DOOR
 CASEMENT WINDOW, IMPACT
 TRANSOM WINDOW, IMPACT
 MULLIONS
  
 PROVIDE MULLION PRODUCT APPROVALS.
  
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE NOA
 SUBMITTED.WWW.FLORIDABUILDING.ORG.IF
 A STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, PLEASE ADVISE AND A LOCAL
 PRODUCT APPROVAL WILL BE ISSUED.
  
 TWO COPIES OF ALL DOCUMENTS REQUIRED,
 ONLY ONE SET OF PRODUCT APPROVALS
 SUBMITTED.
  
 FOR THE MODIFIED PRODUCT APPROVAL,
 SELECT WHICH APPROVED ASSEMBLY YOU WILL
 BE USING.
  
 FOR THE MODIFIED PRODUCT APPROVAL,
 SPECIFY THE ENHANCED FASTENING FOR ZONE
 2 AND ZONE 3.THIS MAY BE DONE BY THE
 CONTRACTOR.
  
 FOR THE METAL ROOF, SELECT WHICH
 APPROVED ASSEMBLY YOU WILL BE USING.IF
 THE ASSEMBLY REQUIRES ENHANCED
 FASTENING, PROVIDE CALCULATIONS AS
 REQUIRED BY THE PRODUCT APPROVAL.SEE
 PAGE 8.
  
 12.)FBC1503.4.2, PROVIDE SCUPPER SIZE
 AND HEIGHT ABOVE ROOF SURFACE, 3-A504.
  
 SIZE WAS PROVIDED, NO DIMENSION FOR THE
 DISTANCE ABOVE THE ROOF.
  
 13-14.)ADDRESSED.
  
 15.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 NEW COMMENTS:
  
 16.)SEPARATE PERMIT REQUIRED FOR THE
 WALL AT THE PERIMETER.
  
 17.)FIREBLOCKING REQUIRED AT THE TOP
 OF THE WALL, FBC705.3.1.
  
 18.)THE PRESSURES FOR ZONE 3, FLAT
 ROOF, ARE INCORRECT, S301, FBC TABLE
 1606.2B.
  
 19.)SEE ATTACHED FS552.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS ARE NOT ADDRESSED A THIRD TIME.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved