| Date |
Text |
| 2006-04-18 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | SECOND REVIEW.FROM PREVIOUS LIST, |
| | NUMBERING REMAINING THE SAME FOR |
| | CONSISTENCY |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | NOT ADDRESSED. |
| | |
| | 3.)PROVIDE A SURVEY FOR THIS PROPERTY. |
| | |
| | ADDRESSED.PLEASE KEEP THIS IN THE |
| | PACKAGE. |
| | |
| | 4.)PROVIDE A SOILS INVESTIGATION |
| | REPORT FBC1804.2.2. |
| | |
| | ONLY ONE WAS PROVIDED.TWO ORIGINALS OF |
| | ALL DOCUMENTS REQUIRED FOR PERMITTING. |
| | |
| | 5.)THE ACCESSIBLE PARKING SPACE DOES |
| | NOT COMPLY WITH CITY OF WEST PALM BEACH |
| | STANDARDS, SEE ATTACHED. |
| | |
| | NOT ADDRESSED. |
| | |
| | 6-7.)ADDRESSED. |
| | |
| | 8.)DECLARE AN OCCUPANT LOAD, FBC10. |
| | |
| | THE OCCUPANT LOAD CANNOT BE LESS THAN |
| | TABLE FBC1003.1, FBC1003.1.1.FRACTIONS |
| | TO BE ROUNDED UP, AS ROUNDING DOWN MAKES |
| | THIS LESS THAN THE NUMBER IN THE TABLE. |
| | |
| | 9.)ADDRESSED. |
| | |
| | 10.)A100 STATES THAT THE BUILDING LOT |
| | COVERAGE IS 2056.4 SF.A101 STATES THAT |
| | THE SHOWROOM IS 1182 SF, STORAGE 303 SF. |
| | ENERGY CALCS STATE THAT THE CONDITIONED |
| | AREA IS 1682.ADDRESS. |
| | |
| | ENERGY CALCS ARE NOT CONSISTENT TO THE |
| | SF DECLARED ON THE PLAN. |
| | |
| | 11.)PROVIDE STATE OR LOCAL PRODUCT |
| | APPROVAL FOR THE FOLLOWING AS PER |
| | FAC9B72: |
| | MODIFIED ROOF; INDICATE APPROVED |
| | ASSEMBLY |
| | STANDING SEAM |
| | OVERHEAD DOOR |
| | FRONT DOOR |
| | METAL DOOR |
| | CASEMENT WINDOW, IMPACT |
| | TRANSOM WINDOW, IMPACT |
| | MULLIONS |
| | |
| | PROVIDE MULLION PRODUCT APPROVALS. |
| | |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE NOA |
| | SUBMITTED.WWW.FLORIDABUILDING.ORG.IF |
| | A STATE PRODUCT APPROVAL IS NOT |
| | AVAILABLE, PLEASE ADVISE AND A LOCAL |
| | PRODUCT APPROVAL WILL BE ISSUED. |
| | |
| | TWO COPIES OF ALL DOCUMENTS REQUIRED, |
| | ONLY ONE SET OF PRODUCT APPROVALS |
| | SUBMITTED. |
| | |
| | FOR THE MODIFIED PRODUCT APPROVAL, |
| | SELECT WHICH APPROVED ASSEMBLY YOU WILL |
| | BE USING. |
| | |
| | FOR THE MODIFIED PRODUCT APPROVAL, |
| | SPECIFY THE ENHANCED FASTENING FOR ZONE |
| | 2 AND ZONE 3.THIS MAY BE DONE BY THE |
| | CONTRACTOR. |
| | |
| | FOR THE METAL ROOF, SELECT WHICH |
| | APPROVED ASSEMBLY YOU WILL BE USING.IF |
| | THE ASSEMBLY REQUIRES ENHANCED |
| | FASTENING, PROVIDE CALCULATIONS AS |
| | REQUIRED BY THE PRODUCT APPROVAL.SEE |
| | PAGE 8. |
| | |
| | 12.)FBC1503.4.2, PROVIDE SCUPPER SIZE |
| | AND HEIGHT ABOVE ROOF SURFACE, 3-A504. |
| | |
| | SIZE WAS PROVIDED, NO DIMENSION FOR THE |
| | DISTANCE ABOVE THE ROOF. |
| | |
| | 13-14.)ADDRESSED. |
| | |
| | 15.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALCS. |
| | |
| | NEW COMMENTS: |
| | |
| | 16.)SEPARATE PERMIT REQUIRED FOR THE |
| | WALL AT THE PERIMETER. |
| | |
| | 17.)FIREBLOCKING REQUIRED AT THE TOP |
| | OF THE WALL, FBC705.3.1. |
| | |
| | 18.)THE PRESSURES FOR ZONE 3, FLAT |
| | ROOF, ARE INCORRECT, S301, FBC TABLE |
| | 1606.2B. |
| | |
| | 19.)SEE ATTACHED FS552.80(2)(B).A 4X |
| | PLAN REVIEW FEE WILL BE CHARGED IF |
| | COMMENTS ARE NOT ADDRESSED A THIRD TIME. |