| Plan Review Notes For Permit 05090878 |
| Permit Number |
05090878 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 BUILDING | | | FBC-2001 CHAPTER 11 | | | | | | 1. SHT A-101 LUNCH ROOM SINK SHALL | | | COMPLY WITH SECTION 11-4.24 AND ALL | | | SUBSECTIONS. PLEASE PROVIDE A DETAIL | | | SHOWING COMPLIANCE. CLEAR FLOOR SPACE | | | SHALL BE FORWARD APPROACH. | | | 2. SHT A-105 ACCESSIBILITY DETAILS. SHOW | | | THE FOLLOWING INFORMATION: | | | A. 11-4.16.5 FLUSH CONTROLS | | | B. 11-4.19.2 HEIGHT & CLEARANCES - | | | CLEARANCES NOT SHOWN | | | C. 11-4.19.5 FAUCETS | | | D. 11-4.15.1.3(10)(A) PROVISIONS FOR | | | THOSE WHO HAVE BENDING OR STOOPING. | | | 3. SHT A-105 DOOR SHALL NOT SWING INTO | | | THE CLEAR FLOOR SPACE REQUIRED FOR ANY | | | FIXTURE. SECTION 11-4.22.2. DOORS ARE | | | OPENING INTO THE CLEAR FLOOR SPACE OF | | | THE DRINKING FOUNTAIN. | | | 4. A-504 DETAIL OF SCUPPER. SHOW HEIGHT | | | AND WIDTH OF SCUPPER AND IF CIRCULAR | | | SHOW DIAMETER. MINIMUM 4" OPENING | | | REQUIRED. ALSO SHOW THE MEASUREMENT OFF | | | THE ROOF TO THE FLOW LINE. SECTION | | | 1503.4.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|