Plan Review Notes For Permit 05090878
Permit Number 05090878
Review Stop P
Sequence Number 1
Notes
Date Text
2005-11-26 00:00:00DENIED
 REFERENCE: FBC-2001 BUILDING
 FBC-2001 CHAPTER 11
  
 1. SHT A-101 LUNCH ROOM SINK SHALL
 COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. PLEASE PROVIDE A DETAIL
 SHOWING COMPLIANCE. CLEAR FLOOR SPACE
 SHALL BE FORWARD APPROACH.
 2. SHT A-105 ACCESSIBILITY DETAILS. SHOW
 THE FOLLOWING INFORMATION:
 A. 11-4.16.5 FLUSH CONTROLS
 B. 11-4.19.2 HEIGHT & CLEARANCES -
 CLEARANCES NOT SHOWN
 C. 11-4.19.5 FAUCETS
 D. 11-4.15.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE BENDING OR STOOPING.
 3. SHT A-105 DOOR SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE. SECTION 11-4.22.2. DOORS ARE
 OPENING INTO THE CLEAR FLOOR SPACE OF
 THE DRINKING FOUNTAIN.
 4. A-504 DETAIL OF SCUPPER. SHOW HEIGHT
 AND WIDTH OF SCUPPER AND IF CIRCULAR
 SHOW DIAMETER. MINIMUM 4" OPENING
 REQUIRED. ALSO SHOW THE MEASUREMENT OFF
 THE ROOF TO THE FLOW LINE. SECTION
 1503.4.2.
  