Text |
| 2005-11-23 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | 3.)PROVIDE A SURVEY FOR THIS PROPERTY. |
| | |
| | 4.)PROVIDE A SOILS INVESTIGATION |
| | REPORT FBC1804.2.2. |
| | |
| | 5.)THE ACCESSIBLE PARKING SPACE DOES |
| | NOT COMPLY WITH CITY OF WEST PALM BEACH |
| | STANDARDS, SEE ATTACHED. |
| | |
| | 6.)THE APPLICATION STATES THAT WALLS |
| | WILL BE REMOVED AND 1000 SF WILL BE |
| | ADDED.THE PLANS SHOW A NEW STRUCTURE. |
| | PLEASE CLARIFY.THE PLANS SHOULD |
| | CLEARLY SHOW WORK TO BE PERFORMED.NO |
| | DEMO PLAN IS SHOWN. |
| | |
| | 7.)IF THIS IS AN ADDITION, PROVIDE |
| | AREA CALCULATIONS; EXISTING, PROPOSED, |
| | NEW TOTAL. |
| | |
| | 8.)DECLARE AN OCCUPANT LOAD, FBC10. |
| | |
| | 9.)THERE IS A DESIGNATION OF "NON |
| | COMBUSTIBLE STORAGE" FOR ROOM 105.DO |
| | YOU MEAN NON HAZARDOUS FBC704.1.2.2(4)? |
| | |
| | 10.)A100 STATES THAT THE BUILDING LOT |
| | COVERAGE IS 2056.4 SF.A101 STATES THAT |
| | THE SHOWROOM IS 1182 SF, STORAGE 303 SF. |
| | ENERGY CALCS STATE THAT THE CONDITIONED |
| | AREA IS 1682.ADDRESS. |
| | |
| | 11.)PROVIDE STATE OR LOCAL PRODUCT |
| | APPROVAL FOR THE FOLLOWING AS PER |
| | FAC9B72: |
| | MODIFIED ROOF; INDICATE APPROVED |
| | ASSEMBLY |
| | STANDING SEAM |
| | OVERHEAD DOOR |
| | FRONT DOOR |
| | METAL DOOR |
| | CASEMENT WINDOW, IMPACT |
| | TRANSOM WINDOW, IMPACT |
| | MULLIONS |
| | |
| | 12.)FBC1503.4.2, PROVIDE SCUPPER SIZE |
| | AND HEIGHT ABOVE ROOF SURFACE, 3-A504. |
| | 13.)ARCHITECTURALS SHOW STEEL TRUSSES, |
| | STRUCTURALS SHOW WOOD. |
| | |
| | 14.)CLARIFY AS TO WHETHER THE ENTRY |
| | DOOR IS INSWING OR OUTSWING.PLANS ARE |
| | NOT CONSISTENT.PLEASE NOTE THAT |
| | PRODUCT APPROVAL MUST ALSO BE CONSISTENT |
| | WITH PLAN. |
| | |
| | 15.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALCS. |
| | |