| Plan Review Notes For Permit 05090863 |
| Permit Number |
05090863 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-07 00:00:00 | *** DENIED *** | | | 1) JOB ADDRESS MUST APPEAR ON ALL PAGES | | | OF PLANS. | | | | | | 2) MECHANICAL PLANS EQUIPMENT LIST SHOWS | | | AHU IS A 10 SEER AND CONDENSER UNIT IS A | | | 12 SEER, PLEASE SHOW THE SEER OF THE | | | SYSTEM ONLY. AND SHOW THE TOTAL BTU'S. | | | AND SENSIBLE BTU'S. OF THE A/C SYSTEM. | | | | | | 3) PLEASE SHOW ON MECH. PLANS THE SIZE | | | OF THE RETURN AIR GRILL TO THE AIR | | | HANDLER. | | | | | | 4) RETURN AIR TRANSFER DUCTS TO | | | BEDROOMS, THE GRILLS ARE TO SMALL FOR | | | THE DUCTS. | | | | | | 5) SUPPLY AIR DUCT TO SECOND FLOOR | | | CLOSET #2 NEEDS TO BE SIZED. | | | | | | 6) PLEASE EXPLAIN WHY A 7" SUPPLY AIR | | | DUCT IS GOING TO THE SMALL CLOSET IN THE | | | HALL. | | | | | | 7) PLEASE SUBMIT MANUAL D CALCULATIONS | | | FOR RESIDENTIAL DUCT DESIGN, PER 2004 | | | FBC/R M1601.1 AND FBC 13-610.1.ABC.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|