| 2006-08-05 00:00:00 | **********UNSAT *********** |
| | |
| | 1) NOTE: PLEASE CLARIFY UNDERGROUND |
| | SEC'S TO FPL. IF THESE ARE INSTALLED BY |
| | FPL , THEN PLEASE DO NOT INDICATE THE |
| | CONDUCTOR SIZES, AS THESE WILL NOT |
| | CORRELATE WITH FPL. |
| | PLEASE ALSO VERIFY THE DOWNSIZING OF THE |
| | NEURTRAL CONDUCTOR TO A #3. |
| | PLEASE PROVIDE NEUTRAL LOAD CALCULATION |
| | OR FULL SIZE NEUTRAL. |
| | 220.22, 310.15B6 |
| | |
| | 2) NOTE: PLEASE SHOW CONDUIT SIZE FOR |
| | THE UNDERGROUND AND ALSO THE CONDUIT TO |
| | INSIDE PANEL. UNABLE TO VERIFY AT THIS |
| | TIME. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE 210.52C1AS THERE |
| | ARE SOME RECEPTS MISSING . SEE REDLINED |
| | PLANS. |
| | PLEASE SEE AREAS OF COUNTER SPACE, |
| | PLEASE SEE LOCATED NEXT TO STOVE ETC. |
| | |
| | 4) NOTE: PLEASE SEE MISSING ISLAND |
| | GFI RECEPT. 210.52C1-5,210.8A6 |
| | |
| | 5) NOTE: PLEASE SEE THAT ALL ROOM AND |
| | AREA DESIGNATIONS ON PLANS CORRELATE |
| | WITH THE PANEL SCHEDULE. |
| | PLEASE SEE THAT ALL CIRCUITS ON PANEL |
| | SCHEDULE SHALL BE SPECIFIC TO ROOMS AND |
| | AREAS. |
| | IE; LIVING RM RECEPTS, BEDRM #2 |
| | LTS/RECEPTS, HALL LTS ETC ETC. |
| | 408.4 FBC 106.1.2 |
| | **IT IS KNOWN THAT CIRCUITING DURING |
| | CONSTRUCTION WILL CHANGE AND THIS CAN EB |
| | REVISED AT A LATER DATE. |
| | |
| | 6) NOTE: PLEASE SEE ONLY TWO CIRCUITS |
| | ARE BEIGN SHOWNWITH ARC FAULT |
| | PROTECTION FOR ALL BEDRMS LTS, RECEPTS |
| | AND SD'S. PLEASE KNOW, THE CODE HAS |
| | CHANGED FROM PREVIOUSLY SUBMITTED PLANS |
| | UNDER THIS PROJECT TO REQUIRE ARC FAULT |
| | PROTECTION FOR ALL OUTLETS IN BEDRMS. |
| | PLEASE BE SURE TO REVISE AS THE LOAD ON |
| | THESE ONLY TWO CIRCUITS SEEM TO EXCEED |
| | RATINGS. |
| | 210.12B(2002) NEC. 210.52,220 |
| | |
| | 7)NOTE: PLEASE SEE MISSING THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S). |
| | 210.11C3, SHALL BE 20A AND #12. |
| | NO BATH(S) LISTED. |
| | |
| | 8) NOTE: PLEASE BE SURE HE PLANS PROVIDE |
| | THE FOLLOWING MINIMUM CODES AS ADOPTED |
| | FOR DESIGN AND FS/FBC 2004 |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 |
| | NFPA-101. |
| | |
| | 9) NOTE: PLEASE SEE PLANS INDICATE THE |
| | PANEL LOCATED INHALL ON PLANS AND |
| | PANEL SCHEDULE SAY HALL/UTILITY.?? |
| | PLEASE SEE ELECTRICAL PLANS DO NOT SHOW |
| | THE SAME WALL AS SHOWN ON BUILDING |
| | PLANS. |
| | PLEASE ALSO CLARIFY THE MISSING CONTROL |
| | FOR LT(S) IN THE UTILITY RM. 210.70 |
| | |
| | 10) NOTE: PLEASE SEE "J-BOXES" SHOWN ON |
| | PLANS NEED TO BE NOTED FOR "FUTURE FAN |
| | BOXES' IF INDEED FOR FANS. PLEASE SEE |
| | 314.47D |
| | |
| | 11) NOTE: PLEASE SEE PLANS DO NOT SHOWN |
| | LOCATION OF SERVICE ON THE OUTSIDE OF |
| | HOUSE. |
| | 106.1.2 |
| | |
| | 12) NOTE: PLEASE SEE SURVEY PROVIDED IN |
| | PACKAGE IS REQUIRED TO CONTAIN AN |
| | ORIGINAL SIAGNAURE IN ORDER FOR SURVEY |
| | TO BE VALID. PLEASE SEE FAC 61G15-17, FS |
| | 472.025 |
| | |
| | 13) NOTE: PLEASE SEE MISSING THE DINING |
| | ROOM CIRCUITS ON ONE OR MORE OF THE SM |
| | APPL CIRCUITS. 210.11C1,220.16 |
| | |
| | 14) NOTE: PLEASE SEE DISHWASHER AND |
| | DISPOSAL SEEM TO BE SHARED TO THE SAME |
| | RECEPT, HOWEVER PLEASE SEE PANEL DOES |
| | NOT INDICATE A 2-POLE BREAKER. PLEASE |
| | SEE 210.4B |
| | |
| | 15) NOTE: PLEASE SEE MISSING DISCONNECT |
| | AND GROUNDING AT THE DETAACHED BLDG. |
| | PLEASE SHOW ON ELECTRICAL PLANS. |
| | PLEASE SEE PANEL SCHEDULES AND LOAD |
| | CALCULATIONS ARE NOT SHOWN FOR NEW |
| | LOADS. MISSING DEDICATED GDO CIRCUIT ETC |
| | PLEASE SEE 225.31-225.39, 250.32, |
| | 430.30/31 |
| | |
| | 16) NOTE: PLEASE SEE THE ARCH OF RECORD |
| | ONCE MOVING THE ELECTRICAL TO E-PLANS, |
| | SHALL SIGN AND SEAL PLANS AS THE |
| | STRUCTURAL ENGINEER IS ONLY FOR STRUCT. |
| | |
| | ** IMPORTANT ** |
| | BEFORE RESUBMITTING PLANS ONCE ALL |
| | REVIEWS ARE COMPLETED. PLEASE BE SURE TO |
| | COMPLETELY REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT THE NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONLY ONE COPY OF THE OLD SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |