| 2007-01-22 14:04:37 | BUILDING REVISION SECOND CHECKLIST (REVISION DONE UNDER |
| | FBC 2004 AS SPECIFIED ON PLANS): |
| | 1- TRUSS DRAWINGS WILL BE REQUIRED FOR REVIEW PRIOR TO |
| | INSTALLATION. SEE SEC. R802.10 FOR REQUIRED |
| | INFORMATION. DESIGNER OF RECORD TO REVIEW AND APPROVE |
| | THEM PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 2- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF |
| | BEING RECORDED IF WORK IS NOT STARTED. SEC. 713.13(2) |
| | FLORIDA STATUTES. NEED RE-RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |
| | 3- A) REVISE THE ENERGY CALCULATIONS. OVERHANG LENGTH |
| | AND OVERHANG HEIGHT ARE INCORRECT. |
| | |
| | B) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| | |
| | 4- BRING DRAWINGS TO PALM BEACH COUNTY FOR IMPACT FEES |
| | REVISION. BRING BACK STAMPED DRAWINGS AND PAID RECEIPT |
| | IF ADDITIONAL FEES ARE DUE. |
| | |
| | 5- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS |
| | UNDER A SEPARATE PERMIT AS AGREED ON AT TIME OF |
| | ORIGINAL PERMIT APPLICATION APPROVAL. |
| | |
| | 6- OWES $788.35ADDITIONAL FEES FOR UPDATED BUILDING |
| | VALUATION,RADON FEES AND REVISION FEES.. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| | B) IMPACT SLIDING GLASS DOORS AS SPECIFIED ON |
| | PLANS. |
| | C) PRECAST CONCRETE LINTELS AS SPECIFIED ON PLANS. |
| | D) ALL SIMPSON OR USP CONNECTORS SPECIFIED ON |
| | FRAMING PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE AND THE SPECIFIC PAGE |
| | SHOWING THE CONNECTOR. |
| | E) SINGLE HUNG WINDOWS. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITTING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | PRODUCT APPROVAL FOR TIBERLINE SHINGLES IS MISSING THE |
| | ARCHITECT'S SIGNATURE. |
| | |
| | 9- ARCHITECT TO PROVIDE ALL HIS INFORMATION AND FIRM'S |
| | INFORMATION AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA |
| | ADMINISTRATIVE CODE. MISSING THE FIRM'S NUMBER. |
| | |
| | 10- SHEET A-2.1: |
| | A) FLOOR PLAN CALLS FOR ONE 16'X7' GARAGE DOOR. |
| | ELEVATION SHOWS 2 SMALL GARAGE DOORS.PRODUCT APPROVAL |
| | FOR GARAGE DOORS DON'T SHOW DOOR TO LOOK LIKE 2 DOORS |
| | IN ONE. HOW IS THIS ACHIEVED. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004 |
| | |
| | 11- SHEET S-2: |
| | A) DETAIL 1/S-2 CALLS FOR (3)2X4 STUDS, WHILE 2ND |
| | FLOOR FRAMING PLAN CALLS FOR (4)2X4 STUDS. |
| | CLARIFY/REVISE AS REQUIRED TO MATCH. |
| | |
| | 19- SHEET S-3: |
| | A) REVISE PLYWOOD SHEATHING NAILING SCHEDULE FOR |
| | ROOF SHEATHING AT ZONE 3. SEE TABLE 2304.9.1 FBC 2004 |
| | AND REVISE AS REQUIRED. |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |