| Date |
Text |
| 2006-08-10 00:00:00 | **********UNSAT *********** |
| | |
| | 1) NOTE: PLEASE CLARIFY UNDERGROUND |
| | SEC'S TO FPL. IF THESE ARE INSTALLED BY |
| | FPL , THEN PLEASE DO NOT INDICATE THE |
| | CONDUCTOR SIZES, AS THESE WILL NOT |
| | CORRELATE WITH FPL. |
| | PLEASE ALSO VERIFY THE DOWNSIZING OF THE |
| | NEURTRAL CONDUCTOR TO A #3. |
| | PLEASE PROVIDE NEUTRAL LOAD CALCULATION |
| | OR FULL SIZE NEUTRAL. |
| | 220.22, 310.15B6 |
| | |
| | 2) NOTE: PLEASE SHOW CONDUIT SIZE FOR |
| | THE UNDERGROUND AND ALSO THE CONDUIT TO |
| | INSIDE PANEL. UNABLE TO VERIFY AT THIS |
| | TIME. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE 210.52 AS THERE ARE |
| | SOME RECEPTS MISSING . SEE REDLINED |
| | PLANS. |
| | PLEASE SEE AREA OF WALL OFF KITCHEN AND |
| | WHAT APPEARS TO BE THE MASTER BEDRM. |
| | |
| | 4) NOTE: PLEASE SEE MISSING PENINSULAR |
| | GFI RECEPT. 210.52C3,210.8A6 |
| | |
| | 5) NOTE: PLEASE PROVIDE ALL ROOM AND |
| | AREA DESIGNATIONS ON PLANS AND CORRELATE |
| | WITH THE PANEL SCHEDULE. |
| | PLEASE SEE THAT ALL CIRCUITS ON PANEL |
| | SCHEDULE SHALL BE SPECIFIC TO ROOMS AND |
| | AREAS. |
| | IE; LIVING RM RECEPTS, BEDRM #2 |
| | LTS/RECEPTS, HALL LTS ETC ETC. |
| | 408.4 FBC 106.1.2 |
| | **IT IS KNOWN THAT CIRCUITING DURING |
| | CONSTRUCTION WILL CHANGE AND THIS CAN EB |
| | REVISED AT A LATER DATE. |
| | |
| | 6) NOTE: PLEASE SEE ONLY TWO CIRCUITS |
| | ARE BEIGN SHOWNWITH ARC FAULT |
| | PROTECTION FOR ALL BEDRMS LTS, RECEPTS |
| | AND SD'S. PLEASE KNOW, THE CODE HAS |
| | CHANGED FROM PREVIOUSLY SUBMITTED PLANS |
| | UNDER THIS PROJECT TO REQUIRE ARC FAULT |
| | PROTECTION FOR ALL OUTLETS IN BEDRMS. |
| | PLEASE BE SURE TO REVISE AS THE LOAD ON |
| | THESE ONLY TWO CIRCUITS SEEM TO EXCEED |
| | RATINGS. |
| | 210.12B(2002) NEC. 210.52,220 |
| | |
| | 7)NOTE: PLEASE SEE MISSING THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S). |
| | 210.11C3, SHALL BE 20A AND #12. |
| | NO BATH(S) LISTED. |
| | |
| | 8) NOTE: PLEASE BE SURE HE PLANS PROVIDE |
| | THE FOLLOWING MINIMUM CODES AS ADOPTED |
| | FOR DESIGN AND FS/FBC 2004 |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 |
| | NFPA-101. |
| | |
| | 9) NOTE: PLEASE SEE PLANS INDICATE THE |
| | PANEL LOCATED IN GARAGE, YET PANEL |
| | MENTIONS THIS IN HALL/UTILITY. |
| | |
| | 10) NOTE: PLEASE SEE MIN EGRESS LIGHTING |
| | IS REQUIRED FOR WHAT APPEARS TO BE |
| | DINGIN AND LIV RM FOR EGRESS. SHOWS ONLY |
| | A JUNCTION BOX FOR FUTURE FAN. PLEASE |
| | KNOW, THIS CAN BE EITHER PROVIDED BY THE |
| | SWITCHING OF A RECEPT OR A LT FIXTURE OF |
| | SOME TYPE WHICH SHALL BE PROIVIDED. |
| | 210.70, LS101 7.8 |
| | |
| | 11) NOTE: PLEASE SEE PLANS SHOWS A METER |
| | AND A MAIN DISCONNECT ON THE OUTSIDE. IF |
| | THIS IS THE CASE, PLEASE REVISE RISER TO |
| | INCLUDE THIS MAIN AND ALSO INCLUDE |
| | EQUIPMENT GROUNDING CONDUCTORS AS |
| | REQUIRED. |
| | 250.24B, 250.122 |
| | 106.1.2 |
| | |
| | 12) NOTE: PLEASE SEE SURVEY PROVIDED IN |
| | PACKAGE IS REQUIRED TO CONTAIN AN |
| | ORIGINAL SIAGNAURE IN ORDER FOR SURVEY |
| | TO BE VALID. PLEASE SEE FAC 61G15-17, FS |
| | 472.025 |
| | |
| | 13) NOTE: PLEASE SEE MISSING THE DINING |
| | ROOM CIRCUITS ON ONE OR MORE OF THE SM |
| | APPL CIRCUITS. 210.11C1,220.16 |
| | |
| | 14) NOTE: PLEASE SEE 210.4B AS THE |
| | DISHWASHER/DISPOSAL ARE FROM THE SAME |
| | RECEPT, HOWEVER THESE ARE ON 1-POLE |
| | BREAKERS. THIS REQUIRES A 2-POLE BRKR. |
| | |
| | 15) NOTE: PLEASE SEE COUNTER SPACE IN |
| | KTICHEN AS IT SEEMS IT IS MISSING GFI |
| | RECEPT(S). PLEASE SEE 210.52C1 AND |
| | REDLINED PLANS. |
| | |
| | 16) NOTE: PLEASE SEE "S" SHEETS AS THESE |
| | ARE MISSING THE REQUIRED CERTIFICATE OF |
| | AUTHORIZATION NUMBER FOR ENGINEERING |
| | FIRM. |
| | FAC 61G15-23.002, FS 471.023 |
| | |
| | ** IMPORTANT ** |
| | BEFORE RESUBMITTING PLANS ONCE ALL |
| | REVIEWS ARE COMPLETED. PLEASE BE SURE TO |
| | COMPLETELY REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT THE NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONLY ONE COPY OF THE OLD SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |