| 2006-11-16 11:34:34 | BUILDING REVISION CHECKLIST (REVISION DONE UNDER FBC |
| | 2004 AS SPECIFIED ON PLANS): |
| | 1- SHEET A-1.0: |
| | A) REVISE TYPE OF CONSTRUCTION. SEE SEC. 602 FBC |
| | 2004. TYPE OF CONSTRUCTION SHOWN ON PLANS APPLIES TO |
| | TYPE IIIB. |
| | B) ADD 2004 FLORIDA RESIDENTIAL CODE, WHICH IS THE |
| | ONE THAT APPLIES TO SINGLE FAMILY RESIDENCES. |
| | C) AREA CALCULATIONS ON SHEET A-1.0 ARE DIFFERENT |
| | THAN THOSE SHOWN ON SHEET A-1.1. REVISE AS REQUIRED. |
| | |
| | 2- TRUSS DRAWINGS WILL BE REQUIRED FOR REVIEW PRIOR TO |
| | INSTALLATION. SEE SEC. R802.10 FOR REQUIRED |
| | INFORMATION. |
| | |
| | 3- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF |
| | BEING RECORDED IF WORK IS NOT STARTED. SEC. 713.13(2) |
| | FLORIDA STATUTES. NEED RE-RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |
| | 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY CHAPTER |
| | 13 FBC 2004. |
| | |
| | 5- BRING DRAWINGS TO PALM BEACH COUNTY FOR IMPACT FEES |
| | REVISION. BRING BACK STAMPED DRAWINGS AND PAID RECEIPT |
| | IF ADDITIONAL FEES ARE DUE. |
| | |
| | 6- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS |
| | UNDER A SEPARATE PERMIT AS AGREED ON AT TIME OF |
| | ORIGINAL PERMIT APPLICATION APPROVAL. |
| | |
| | 7- OWES ADDITIONAL FEES FOR UPDATED BUILDING VALUATION |
| | AND RADON FEES. FEES WILL BE CALCULATED WHEN ITEM 1(C) |
| | ABOVE IS CLARIFIED. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| | B) IMPACT SLIDING GLASS DOORS AS SPECIFIED ON |
| | PLANS. |
| | C) PRECAST CONCRETE LINTELS AS SPECIFIED ON PLANS. |
| | D) ALL SIMPSON OR USP CONNECTORS SPECIFIED ON FRAMING |
| | PLANS AND DETAILS. |
| | E) GARAGE DOOR. NEED CLEAR AND LEGIBLE DRAWINGS. |
| | CLARIFY IF USING THE DADE COUNTY NOA OR FLORIDA PRODUCT |
| | APPROVAL 4861. PROVIDE COMPLETE PACKAGE FOR EITHER ONE, |
| | BUT DON'T MISMATCH ONE WITH THE OTHER. |
| | F) ASPHALT SHINGLES. DOWNLOAD DADE COUNTY NOA |
| | 04-0305.03 WHICH IS THE CORRECT NOA THAT WAS SUBMITTED |
| | TO OBTAIN FLORIDA PRODUCT APPROVAL #FL183-R1. GO TO |
| | WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL INFORMATION. G) |
| | SINGLE HUNG WINDOWS. |
| | |
| | 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITTING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 10-SPECIFY SAFETY GLASS IN WINDOW LOCATED IN MASTER |
| | BATH TUB. SEC. R308.4 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 11- 2ND FLOOR ATTIC ACCESS SHALL BE IN HALLWAY OR |
| | ALREADY ACCESSIBLE LOCATION. REVISE AS REQUIRED. SEC. |
| | R807.1 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 12- ENGINEER TO PROVIDE ALL HIS INFORMATION AND FIRM'S |
| | CERTIFICATE OF AUTHORIZATION AS REQUIRED BY SEC. |
| | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 13- ARCHITECT TO PROVIDE ALL HIS INFORMATION AND FIRM'S |
| | INFORMATION AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 14- SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY |
| | CHAPTER 472 FLORIDA STATUTES. |
| | |
| | 15- SHEET A-2.1: |
| | A) FLOOR PLAN CALLS FOR ONE 16'X7' GARAGE DOOR. |
| | ELEVATION SHOWS 2 SMALL GARAGE DOORS. CLARIFY/REVISE AS |
| | REQUIRED TO MATCH. |
| | B) REVISE ELEVATIONS ORIENTATION. SEE SURVEY FOR |
| | CORRECT ORIENTATION. |
| | |
| | 16- SHEET A-3.1: |
| | A) PORCH SECTION AND TYP. WALL SECTION CALL FOR |
| | "ASPHALT TILE ROOF". CLARIFY WHAT IS IT?. REVISE AS |
| | REQUIRED. |
| | B) CHANGES DONE BY HAND ARE NOT ACCEPTABLE. EG: |
| | STUCCO THICKNESS. REVISE ORIGINAL DRAWINGS AS |
| | REQUIRED. |
| | |
| | 17- SHEET A-4.1: |
| | A) DETAIL #1 IS FOR WINDOW AND DOOR BUCK DETAIL. |
| | CLARIFY TITLE SAYS WINDOW, WHILE DETAIL SAYS DOOR |
| | FRAME. |
| | B) THERE ARE TWO DIFFERENT SPECS FOR BUCK FASTENING. |
| | SEE DETAIL 1 AND WINDOW/DOOR BUCK NOTES ON SHEET S-2 |
| | AND REVISE AS REQUIRED. |
| | C) HURRICANE PANEL DETAIL: EDGE DISTANCE IS |
| | INCORRECT. STUCCO THICKNESS CAN'T BE CONSIDERED FOR |
| | EDGE DISTANCE. REVISE AS REQUIRED. SEE ACTUAL STORM |
| | PANELS PRODUCT APPROVAL. |
| | ***NOTE: THIS DETAIL IS NOT REQUIRED. IT'S EASIER AND |
| | WILL AVOID DISCREPANCIES IF ONLY THE PRODUCT APPROVAL |
| | FOR STORM SHUTTERS IS SUPLLIED WHEN APPROVED BY THE |
| | DESIGNER OF RECORD. |
| | D) SECTION AT REAR PORCH: SPECIFY LEDGERS FOR ROOF |
| | SHEATHING SUPPORT AT MASONRY WALL. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | C) SPECIFY FIREBLOCKING. SEC. R602.8 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 18- SHEET S-2: |
| | A) REVISE WINDOW NOTES. NEED WINDOWS FOR 140 MPH |
| | INSTALLATION, NOT 120. REVISE ORIGINAL DRAWING. HAND |
| | CHANGES ARE NOT ACCEPTABLE. |
| | B) BEARING WALL CONNECTION TO CBS DETAIL AND DETAIL |
| | 1/S-2: CLARIFYIF USING SIMPSON OR USP CONNECTORS. C) |
| | DETAIL 1/S-2 CALLS FOR (3)2X4 STUDS, WHILE 2ND FLOOR |
| | FRAMING PLAN CALLS FOR (4)2X4 STUDS. CLARIFY/REVISE AS |
| | REQUIRED TO MATCH. |
| | D) SPECIFY ROOF TRUSS CONNECTORS FOR REAR PORCH |
| | ROOF. |
| | |
| | 19- SHEET S-3: |
| | A) REVISE PLYWOOD SHEATHING NAILING SCHEDULE FOR |
| | ROOF SHEATHING. SEE TABLE 2304.9.1 FBC 2004 AND REVISE |
| | AS REQUIRED. |
| | B) SPECIFICATION GIVENON PLYWOOD SHEATHING NAILING |
| | SCHEDULE AND OVERHANG DETAIL DON'T MATCH. REVISE AS |
| | REQUIRED. |
| | C) CONNECTOR SCHEDULE: REVISE UPLIFT AND FASTENERS |
| | SPECIFIED FOR SIMPSON HETAL 16 AND SP4. SEE CURRENT |
| | CATALOGUE AND UPDATE AS REQUIRED. OTHERWISE, PROVIDE |
| | COMPLETE ENGINEERING ANALYSIS FOR VALUES AND NUMBERS |
| | THAT ARE DIFFERENT FROM THOSE TESTED AND PUBLISHED BY |
| | MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | D) MAXIMUM DESIGN PRESSURES SHOWN ARE LOW COMPARED |
| | TO TABLE 1609.6B OR TABLES IN ASCE 7-02.PROVIDE |
| | ACTUAL CALCULATIONS SHOWING HOW THE MAXIMUM POSITIVE |
| | AND NEGATIVE LOADS ARE DETERMINED. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |