Plan Review Notes
Plan Review Notes For Permit 05090812
Permit Number 05090812
Review Stop E
Sequence Number 3
Notes
Date Text
2006-08-05 00:00:00************ UNSAT ************
  
 1) NOTE: PLEASE SEE 225.31-225.39, FOR
 FEEDS GOING TO GARAGE.
 PLEASE ALSO REVISE MAIN HOUSE PLANS
 SHOWING GARAGE AS ORIG PLANS DID NOT
 INCLUDE CIRUITING ON PANEL SCHEDULE, OR
 DISCONNECTS ETC ON RISER.
  
 2) NOTE: PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM REQUIRED AT THE
 DETACHED GARAGE.
  
  
 3) NOTE: PLEASE ALSO SEE THAT THE PLANS
 SHALL INCLUDE ALL OTHER EXISTING
 ELECTRICAL WHICH IS ACTUALLY NEW AS THE
 HOUSE IS UNDER CONSTRUCTION.
  
 4) NOTE: PLEASE BE SURE THE DESIGNER OF
 RECORD SIGNS, DATES AND SEALS THE
 ELECTRICAL REVISIONS AS THE DESIGNER OF
 RECORD WHICH IS ALREADY ON FILE.
 PLEASE SEE FS 481.025
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]