| 2006-09-17 00:00:00 | ***UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE PLANS NOW INDICATE |
| | THE BUILDINGOUT OF WHAT WAS TO BE THE |
| | "FUTURE TENANT" AND IS BEING |
| | INCORPORATED INTO THE SCOPE OF WORK. |
| | PLEASE SEE AN ADJUSTMENT IN BUILDING |
| | VALUATION IS REQUIRED PER FBC 108.3 |
| | |
| | 2) NOTE: PLEASE PROVIDE CLEAR FLOOR |
| | SPACE LAYOUT FOR ALL ELECTRICAL |
| | EQUIPMENT. PLEASE ALSO NOTE , NO |
| | STORAGE. |
| | PLEASE SEE FIRE REVIEW AS THE NEW BACK |
| | DOOR LOCATION WILL BE THE LIKELY |
| | LOCATION OF THE KNOX BOX WHICH WILL BE |
| | REQUIRED. PLEASE KNOW THIS IS GOING TO |
| | BE THE FIRE MARSHAL'S OFFICE REVIEW NOTE |
| | AND CONSIDERATION SHOULD BE TAKEN FOR |
| | DISTANCE OF TRAVEL INTO BUILDING FOR |
| | SAFETY OF FIRE DEPT PERSONNEL TO TURN |
| | OFF POWER AT THE MAIN. |
| | 230.70 |
| | |
| | 3) NOTE: PLEASE SEE NOTES FROM PREVIOUS |
| | REDLINES WHICH REQUESTED THE TIMES FOR |
| | ALL OVER-RIDE(S) DEVICES. |
| | PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, |
| | .1.3 |
| | |
| | 4) NOTE: PLEASE SUBMIT COMPLETE REVISED |
| | FLORIDA ENERGY CALCULATIONS FOR |
| | INCREASED SPACE FOR BUILD OUT. |
| | FBC 13-101.1.1,13-415.1.AB.1. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |