| Plan Review Notes For Permit 05090770 |
| Permit Number |
05090770 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-10-12 19:29:23 | ---------------DENIED----------------- | | | 1. SUBMIT REVISED ENERGY CALCULATIONS TO INCLUDE NEW | | | EQUIPMENT AND EXPANDED CONDITIONED SPACE. | | | | | | 2. PG.M1.2 BREAK ROOM 110 SHOWS R/A GRILL IN CEILING | | | OPEN TO PLENUM SPACE ABOVE.HOW WILL R/A LEAVE PLENUM | | | SPACE? BALANCED R/A IS REQUIRED PER FBC,M 601.4 | | | | | | 3. PG.M1.2 GOLFTEC BAYS 1,2,3: DO THESE ROOMS HAVE | | | DOORS ON ENTRANCES? IF THERE ARE DOORS, THE R/A | | | OPENINGS IN WALLS (ABOVE CEILING) ARE TOO SMALL TO | | | ACHIEVE BALANCED RETURN PER FBC,M 601.4 EXCEPTION #2 IF | | | THERE ARE NO DOORS ON THESE ROOMS, THEN R/A GRILLS ARE | | | NOT REQUIRED IN CEILINGS OR WALLS. | | | | | | 4. PGM1.2 OFFICE 104: R/A TRANSFER GRILL IS TOO SMALL | | | PER FBC,M 601.4 EXCEPTION #2 | | | | | | 5. PG.M1.2 GENERAL NOTE #7: COMPLIANCE WITH WIND LOAD | | | REQUIREMENTS OF FBC CHAPTER 16 REQUIRES AN ENGINEERED | | | SYSTEM. PLEASE PROVIDE DETAILS FOR CURB-TO-ROOF AND | | | RTU-TO-CURB ATTACHMENTS. NOTE: THE CITY OF WEST PALM | | | BEACH IS IN THE 140MPH WIND ZONE PER FBC CHAPTER 16. | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|