2006-06-18 00:00:00***** PROVISO/REVISION**********
  
 1) NOTE: PLEASE SEE FUTURE TENANT SPACES
 SHALL CONTAIN AUTO SHUT OF OF LIGHTING
 WITH OVER-RIDES DEVICES OF SOME TYPE
 LOCATED IN AN ACCESSIBLE LOCATION AT
 ENTRANCE TO SPACE.
 EITHER A TIMED OVER-RIDE (MAX 4HRS OR
 OCC SENSOR TYPE OVER-RIDE DEVICE (MAX
 30MINS) SHALL BE INDICATED.
  
 2) NOTE: PLEASE LIST TIMES FOR
 OVER-RIDES DEVICES.
 PLEASE SEE UNITS AT FRONT DOOR AND OCC
 SENSORS.
  
 ** FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2,.1.3 ETC.
  
 *** IMPORTANT**
 THIS REVISION ALONG WITH ANY OTHER
 REVISIONS ARE TO BE SUBMITTED TO THE
 CITY FOR REVIEW AND STAMPING "BEFORE
 ROUGH" ELECTRICAL INSPECTION IS CALLED
 IN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
 ******* NOTE ALSO ADDED TO FRONT SCREEN*
  
  
 PLEASE SEE NOTICE OF COMMENCMENT
 SUBMITTED WHICH WAS RECORDED ON FEB 10,
 2006 HAS EXPIRED AS WORK HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORD NOC
 AND NOC HAS NOW BECOME "VOID".
 PLEASE SEE FS 7.13.13(2).
  
 A NEW NOC WILL BE REQUIRED BEFORE
 PICKING UP PERMIT.