| 2006-06-18 00:00:00 | ***** PROVISO/REVISION********** |
| | |
| | 1) NOTE: PLEASE SEE FUTURE TENANT SPACES |
| | SHALL CONTAIN AUTO SHUT OF OF LIGHTING |
| | WITH OVER-RIDES DEVICES OF SOME TYPE |
| | LOCATED IN AN ACCESSIBLE LOCATION AT |
| | ENTRANCE TO SPACE. |
| | EITHER A TIMED OVER-RIDE (MAX 4HRS OR |
| | OCC SENSOR TYPE OVER-RIDE DEVICE (MAX |
| | 30MINS) SHALL BE INDICATED. |
| | |
| | 2) NOTE: PLEASE LIST TIMES FOR |
| | OVER-RIDES DEVICES. |
| | PLEASE SEE UNITS AT FRONT DOOR AND OCC |
| | SENSORS. |
| | |
| | ** FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| | .1.2,.1.3 ETC. |
| | |
| | *** IMPORTANT** |
| | THIS REVISION ALONG WITH ANY OTHER |
| | REVISIONS ARE TO BE SUBMITTED TO THE |
| | CITY FOR REVIEW AND STAMPING "BEFORE |
| | ROUGH" ELECTRICAL INSPECTION IS CALLED |
| | IN. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | ******* NOTE ALSO ADDED TO FRONT SCREEN* |
| | |
| | |
| | PLEASE SEE NOTICE OF COMMENCMENT |
| | SUBMITTED WHICH WAS RECORDED ON FEB 10, |
| | 2006 HAS EXPIRED AS WORK HAS NOT |
| | COMMENCED WITHIN 90 DAYS OF RECORD NOC |
| | AND NOC HAS NOW BECOME "VOID". |
| | PLEASE SEE FS 7.13.13(2). |
| | |
| | A NEW NOC WILL BE REQUIRED BEFORE |
| | PICKING UP PERMIT. |