2006-06-21 00:00:00****CORRECTIONS****
 ****THIRD REVIEW (SECOND PERMIT
 REVIEW)****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 FROM PREVIOUS REVIEWS, NUMBERING
 REMAINING THE SAME.
  
 1.)ADDRESSED.PLEASE KEEP THE NOC IN
 THE PACKAGE.
  
 2.)ADDRESSED.PLEASE KEEP IMPACT FEE
 STAMPED PAGE AND RECEIPT IN THE PACKAGE.
  
 3.-5.)ADDRESSED.
  
 6.)THIRD REQUEST FOR THREE SETS OF
 PLANS.ONLY TWO SUBMITTED.
  
 7.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS, FBC13-103.1.
  
 (2ND REVIEW) THIS WAS SIGNED.HOWEVER,
 SEE OTHER
 CORRECTIONS REGARDING ENERGY CALCS.IF
 NEW ENERGY CALCS ARE PRODUCED PLEASE
 SIGN THE NEW CALCS.THREE COPIES ARE
 REQUIRED.
  
 (3RD REVIEW) SEE OTHER COMMENTS
 REGARDING ENERGY CALCS.SUBMIT THREE
 COPIES, ONLY ONE NEW AND TWO OLD ENERGY
 CALCS SUBMITTED.
  
 8-11.)ADDRESSED.
  
 12.)IT APPEARS THAT ALL REFERENCES
 HAVE BEEN REVISEDEXCEPT THAT S-001
 STILL REFERS TO ACI347R-94.IT IS
 CLOUDED BUT NOT REVISED.
  
 13-23.)ADDRESSED.
  
 COMMENTS FROM 2ND REVIEW, NOT ADDRESSED:
  
 24.)ADDRESSED.
  
 25.)THE ENERGY CALCS, CIVILS, AND
 ARCHITECTURALS CONFLICT AS TO THE
 BUILDING SIZE.NOTE THAT IMPACT FEE
 ASSESSMENT REVISION MAY BE REQUIRED WHEN
 THE ACTUAL BUILDING SIZE IS DETERMINED.
  
 3RD REVIEW ? THE LETTER FROM THE
 ARCHITECT REGARDING THE DISCREPANCY IN
 SQUARE FOOTAGE ON THE ENERGY CALC IS
 ACKNOWLEDGED.PLEASE SEE FBC13-2,
 DEFINITIONS, CONDITIONED FLOOR AREA, TO
 BE MEASURED EXTERIOR FACES OF EXTERIOR
 WALLS.REVISE THE ENERGY CALCS; SQUARE
 FOOT AREA TO MATCH ARCHITECTURAL PLAN.
  
 26.)ADDRESSED
  
 27.)NOTHING ON THE SHEET 5 OF THE
 ENERGY CALCS IS MARKED AS BEING CHECKED.
 THIS IS REQUIRED TO SHOW CODE COMPLIANCE
 FBC13-103.1.1.1.
  
 3RD REVIEW ? NOT ADDRESSED.HOWEVER,
 THIS WAS ON PAGE 5 OF THE OLD ENERGY
 CALC, NOW APPEARS ON PAGE 6.EITHER
 CHECK OR MARK N/A TO SHOW CODE
 COMPLIANCE, CANNOT BE LEFT BLANK.
  
 28-33.)ADDRESSED
  
 33.)PARKING IS TO COMPLY WITH CITY OF
 WEST PALM BEACH STANDARD, SEE ATTACHED.
  
 THE NOTE STATING THAT THEY WILL CONFORM
 TO THE STANDARD IS ACKNOWLEDGED.
 HOWEVER, THE DETAILS ON THE
 ARCHITECTURAL AND CIVIL SHEETS DO NOT
 COMPLY.REVISE.
  
 34.)ADDRESSED.
  
 35.)S103, CLARIFY AS TO WHY TWO OF THE
 CORNERS ARE ZONE 2 RATHER THAN ZONE 3.
 FBC16.
  
 THE RESPONSE FROM THE ARCHITECT THAT
 THOSE CORNERS ARE PROTECTED BY A PARAPET
 WALL IS ACKNOWLEDGED.HOWEVER, SEE
 ASCE7-02, SECTION 6.5.12.4.4 REGARDING
 PARAPETS.SHOW ZONE 3 ON ALL CORNERS AS
 REQUIRED BY ASCE7-02 DESIGN STANDARDS.
  
 THE SHEET WAS REVISED TO STATE FBC2001.
 GOVERNING CODE IS FBC2004.REVISE.
  
 36.)ADDRESSED.
  
 37.)PROVIDE A FIRE SPRINKLER PLAN
 FBC*106.3.5.1.1(5).
  
 THE ARCHITECT?S RESPONSE THAT THE
 SPRINKLER PLANS WERE PROVIDED IS
 ACKNOWLEDGED.HOWEVER, I AM UNABLE TO
 FIND THEM IN THE PACKAGE SUBMITTED.
  
 NEW COMMENTS, THIRD REVIEW
  
 38.)ROOF PRESSURES ON THE RAS117
 CALCULATIONS PREPARED BY ACRC ARE LOWER
 FOR ZONE 3 THAN THE PLAN.THIS MAY BE
 SUBMITTED LATER; NOT REQUIRED.
  
 39.)THE FIRE SPRINKLER ENGINEERING IS
 TO COMPLY WITH ALL REQUIREMENTS OF
 FAC61G15-23.002 (TITLE BLOCK, INDEX
 SHEET).THIS MAY BE SUBMITTED LATER
 WITH THE FIRE SPRINKLER PERMIT
 APPLICATION.
  
 40.) THE CERTIFICATE OF FLAME RESISTANCE
 SUBMITTED FOR THE AWNING FABRIC DOES NOT
 SHOW COMPLIANCE WITH FBC3105.3.1.
 PLEASE NOTE THAT THIS INFORMATION IS NOT
 REQUIRED AT THIS TIME; THIS CAN BE
 PROVIDED WITH THE AWNING PERMIT
 APPLICATION.
  
 41.) PLEASE REVISE THE ADDRESS ON THE
 PLANS.THIS MAY BE DONE BY HAND.I
 APOLOGIZE THAT I AGREED THAT THIS MAY BE
 DONE BY LETTER; HOWEVER, I DID NOT
 REALIZE AT THAT TIME THAT THE ADDRESS ON
 THE PLAN WAS NOT THE ADDRESS FOR THE
 PARCEL.THE ADDRESS SHOWN ON THE PLAN,
 201 EXECUTIVE CENTER DRIVE, DOES NOT
 EXIST.I THOUGHT THAT THE ADDRESS ON
 THE PLAN WAS 715 W EXECUTIVE CENTER
 DRIVE, WHICH IS THE SAME PARCEL AS 785 W
 EXECUTIVE CENTER DRIVE.MY APOLOGIES
 FOR ANY INCONVENIENCE.
  
 42.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE IS REQUIRED TO BE
 CHARGED IF THE CORRECTIONS ARE NOT
 ADDRESSED A THIRD TIME.