| Notes |
| Date |
Text |
| 2006-03-25 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | DENIED | | | | | | 1) SHT 1.3 PLUMBING RISER DIAGRAM. | | | 606.1 LOCATION OF FULL-OPEN VALVES. | | | FULL-OPEN VALVES SHALL BE INSTALLED IN | | | THE FOLLOWING LOCATIONS: | | | (4). ON THE TOP OF EVERY WATER DOWN-FEED | | | PIPE IN OCCUPANCIES OTHER THAN ONE- AND | | | TWO-FAMILY RESIDENTIAL OCCUPANCIES. | | | 2) SHT.P1.0WATER HEATER DETAIL. | | | PROVIDE A VACUN RELIEF VALVE. | | | " NOT A VACUM BREAKER." | | | 504.2 VACUUM RELIEF VALVE. | | | BOTTOM FED WATER HEATERS AND BOTTOM FED | | | TANKS CONNECTED TO WATER HEATERS SHALL | | | HAVE A VACUUM RELIEF VALVE INSTALLED. | | | THE VACUUM RELIEF VALVE SHALL COMPLY | | | WITH ANSI Z21.22. | | | 3)SHT A2.0,A2.1 PREVIOUS COMMENT: | | | REMOVE THE TURNING CIRCLE FROM BOTH | | | STALLS. SEC.11-4.22.3 | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|