2006-03-25 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 DENIED
  
 1) SHT 1.3 PLUMBING RISER DIAGRAM.
 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN
 THE FOLLOWING LOCATIONS:
 (4). ON THE TOP OF EVERY WATER DOWN-FEED
 PIPE IN OCCUPANCIES OTHER THAN ONE- AND
 TWO-FAMILY RESIDENTIAL OCCUPANCIES.
 2) SHT.P1.0WATER HEATER DETAIL.
 PROVIDE A VACUN RELIEF VALVE.
 " NOT A VACUM BREAKER."
 504.2 VACUUM RELIEF VALVE.
 BOTTOM FED WATER HEATERS AND BOTTOM FED
 TANKS CONNECTED TO WATER HEATERS SHALL
 HAVE A VACUUM RELIEF VALVE INSTALLED.
 THE VACUUM RELIEF VALVE SHALL COMPLY
 WITH ANSI Z21.22.
 3)SHT A2.0,A2.1 PREVIOUS COMMENT:
 REMOVE THE TURNING CIRCLE FROM BOTH
 STALLS. SEC.11-4.22.3
  
 END OF COMMENTS, QUESTIONS 561-805-6692