2006-03-29 00:00:00******DENIED******
  
 1) THE REQUIRED FIRE EXTINGUISHERS SHALL
 BE 2A-10B,C RATED AND MOUNTED AT
 DISTANCES TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 2) FIRE SPRINKLER AND FIRE ALARM LAYOUTS
 ARE NOT PROVIDED WITH SUBMITTAL. PLEASE
 NOTE THAT SEPARATE SHOP DRAWINGS AND
 PERMITS ARE REQUIRED FOR FIRE SPRINKLER
 AND FIRE ALARM SYSTEMS.
  
 3) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
 DOCUMENTATION OF THE CERTIFICATE
 REQUIRED AT TIME OF FIRE ALARM FINAL
 INSPECTION.
  
 4) PLEASE PROVIDE SPECIFIC DETAILS
 REGARDING MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 5) PLEASE PROVIDE FURTHER INFORMATION IN
 REFERENCE TO AUTOMATIC SHUT DOWN ON SHT
 A0.1.
  
 6) A KNOX BOX IS REQUIRED AND
 APPLICATION CAN BE OBTAINED THROUGH THE
 BUREAU OF FIRE PREVENTION.
  
 7) SHT A0.1 REFERENCES FIRE ALARM DEVICE
 LAYOUT ON ELECTRICAL SHEETS. IT DOES NOT
 APPEAR THAT ALL DEVICES AND ASSOCIATED
 EQUIPMENT, CONTROL PANEL ETC ARE
 ILLUSTRATED.
  
 8) DOOR #6 INDICATES 210 OCCUPANTS. A
 MAXIMUM OF 180 PERSONS IS ALLOWABLE
 BASED ON THE CALCULATION OF 0.2" PER
 PERSON.
  
 9) RAMPS SHALL HAVE HANDRAILS ON BOTH
 SIDES.
  
 10) PLEASE NOTE THAT THE WRONG EDITION
 OF NFPA 101 HAS BEEN REFERENCED ON SHT
 A8.0.
  
 11) PLEASE PROVIDE FLAME RETARDANT
 CERTIFICATION FOR AWNINGS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  