| 2006-03-29 00:00:00 | ******DENIED****** |
| | |
| | 1) THE REQUIRED FIRE EXTINGUISHERS SHALL |
| | BE 2A-10B,C RATED AND MOUNTED AT |
| | DISTANCES TO SATISFY THE 75' TRAVEL |
| | DISTANCE REQUIREMENT. |
| | |
| | 2) FIRE SPRINKLER AND FIRE ALARM LAYOUTS |
| | ARE NOT PROVIDED WITH SUBMITTAL. PLEASE |
| | NOTE THAT SEPARATE SHOP DRAWINGS AND |
| | PERMITS ARE REQUIRED FOR FIRE SPRINKLER |
| | AND FIRE ALARM SYSTEMS. |
| | |
| | 3) FIRE ALARM SYSTEM SHALL BE UL |
| | CERTIFIED FOR CENTRAL STATION SERVICE. |
| | DOCUMENTATION OF THE CERTIFICATE |
| | REQUIRED AT TIME OF FIRE ALARM FINAL |
| | INSPECTION. |
| | |
| | 4) PLEASE PROVIDE SPECIFIC DETAILS |
| | REGARDING MINIMUM INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILING. |
| | |
| | 5) PLEASE PROVIDE FURTHER INFORMATION IN |
| | REFERENCE TO AUTOMATIC SHUT DOWN ON SHT |
| | A0.1. |
| | |
| | 6) A KNOX BOX IS REQUIRED AND |
| | APPLICATION CAN BE OBTAINED THROUGH THE |
| | BUREAU OF FIRE PREVENTION. |
| | |
| | 7) SHT A0.1 REFERENCES FIRE ALARM DEVICE |
| | LAYOUT ON ELECTRICAL SHEETS. IT DOES NOT |
| | APPEAR THAT ALL DEVICES AND ASSOCIATED |
| | EQUIPMENT, CONTROL PANEL ETC ARE |
| | ILLUSTRATED. |
| | |
| | 8) DOOR #6 INDICATES 210 OCCUPANTS. A |
| | MAXIMUM OF 180 PERSONS IS ALLOWABLE |
| | BASED ON THE CALCULATION OF 0.2" PER |
| | PERSON. |
| | |
| | 9) RAMPS SHALL HAVE HANDRAILS ON BOTH |
| | SIDES. |
| | |
| | 10) PLEASE NOTE THAT THE WRONG EDITION |
| | OF NFPA 101 HAS BEEN REFERENCED ON SHT |
| | A8.0. |
| | |
| | 11) PLEASE PROVIDE FLAME RETARDANT |
| | CERTIFICATION FOR AWNINGS. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |