Plan Review Notes
Plan Review Notes For Permit 05090770
Permit Number 05090770
Review Stop B
Sequence Number 2
Notes
Date Text
2006-03-24 00:00:00****CORRECTIONS****
 ****SECOND REVIEW (FIRST PERMIT
 REVIEW)****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 FROM PREVIOUS REVIEW, NUMBERING
 REMAINING THE SAME.ITEMS IN CAPITAL
 LETTERS ARE COMMENTS FROM THE SECOND
 REVIEW, WITH THE EXCEPTION OF THE LAST
 ITEMS WHICH ARE NEW COMMENTS.
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 THIS HAS BEEN DONE.PLEASE KEEP THE
 STAMPED SHEET AND THE RECEIPT IN THE
 PACKAGE WHEN RESUBMITTING.
  
 3.)ADDRESSED.
  
 4.-5.)ADDRESSED.
  
 6.)THREE SETS OF PLANS AND ALL
 DOCUMENTS REQUIRED; RESIDENT INSPECTOR
 REQUIRED, FBC*109.3.7.PLEASE CONTACT
 HAROLD PISKURA, 561-805-6711.
  
 NOT ADDRESSED; ONLY TWO COPIES SUBMITTED
 ALTHOUGH THE RESPONSE LETTER STATES THAT
 THREE WERE SUBMITTED.
  
 THE RESPONSE THAT THIS WILL BE DONE
 PRIOR TO CONSTRUCTION IS ACKNOWLEDGED.
 NOTE THAT THIS IS REQUIRED PRIOR TO
 PERMIT ISSUANCE.TO AVOID FURTHER
 DELAYS, CONTACT HAROLD PISKURA AS
 REQUESTED.THE PRECONSTRUCTION MEETING
 AND INSPECTION PLAN APPROVED BY THE CITY
 ARE REQUIRED PRIOR TO PERMIT ISSUANCE.
  
 7.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS, FBC13-103.1.
  
 THIS WAS SIGNED.HOWEVER, SEE OTHER
 CORRECTIONS REGARDING ENERGY CALCS.IF
 NEW ENERGY CALCS ARE PRODUCED PLEASE
 SIGN THE NEW CALCS.THREE COPIES ARE
 REQUIRED.
  
 8.)ADDRESSED.
  
 9.)SUBMIT PRODUCT APPROVALS, FAC9B72:
  
 ROOF
 STOREFRONT SYSTEM
 HOLLOW METAL DOOR
 ROLL UP DOOR
 GLASS BLOCK
  
 IF THE PRODUCTS SELECTED DO NOT MEET
 WORST CASE WIND PRESSURES AS SPECIFIED
 ON S-501, SUBMIT A SCHEDULE SPECIFYING
 PRESSURES FOR EACH OPENING.
  
 FOR THE ROOF PRODUCT APPROVAL, INDICATE
 WHICH APPROVED ASSEMBLY YOU ARE USING.
 SEE S-103 FOR ROOF PRESSURES.
  
 THREE COPIES OF ALL DOCUMENTS REQUIRED.
 ONLY TWO WERE SUBMITTED.
  
 FLORIDA STATE OR LOCAL PRODUCT APPROVALS
 REQUIRED IN ADDITION TO THE NOAS
 PROVIDED, WWW.FLORIDABUILDING.ORG.
 PLEASE ADVISE IF IT IS NOT AVAILABLE FOR
 ANY OF THE PRODUCTS.
  
 PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD FBC*106.3.3.
  
 SEE ABOVE REQUEST IN REGARDS TO THE WIND
 PRESSURES.PROVIDE THE DESIGN PRESSURES
 FOR EACH OPENING ON THE ELEVATIONS
 SHOWN.THE STOREFRONT SYSTEM, AS WELL
 AS OTHER PRODUCTS SUBMITTED, ARE NOT
 COMPLIANT FOR ?WORST CASE?.WORST CASE
 IS 10SF ZONE 5, +50.1/-66.8.SEVERAL OF
 THE PRODUCTS ARE NOT COMPLIANT.
  
 FOR THE GAF BUILT UP ROOF, THE
 ARCHITECT?S RESPONSE LETTER THAT YOU ARE
 USING SYSTEM B2 IS ACKNOWLEDGED.
  
 THE KAWNEER COMPANY SERIES 350-MS DOORS
 ARE NOT TO BE USED WHERE WATER
 INFILTRATION REQUIREMENT IS NEEDED.
 ADDRESS.IF YOU ARE GOING TO USE THIS
 DOOR, WRITE THE DOOR NUMBER DIRECTLY ON
 THE PRODUCT APPROVAL PRIOR TO REVIEW BY
 DESIGNER OF RECORD.DOR IS TO NOTE THAT
 THIS HAS BEEN ADDRESSED.
  
 YKK AP AMERICA YHS-50 DOOR, INDICATE ON
 SHEET 2 OF 6 OF THE PRODUCT APPROVAL
 WHICH CONFIGURATION AND SIZE YOU ARE
 INSTALLING.NOT ALL ARE COMPLIANT FOR
 WIND PRESSURES.
  
 YKK AP AMERICA 35H DOOR, INDICATE WHICH
 SPECIFIC OPTION YOU ARE INSTALLING.NOT
 ALL ARE COMPLIANT FOR WIND PRESSURES.
  
 STEELCRAFT MANUFACTURING STEEL DOOR IS
 NOT APPROVED FOR USE WHERE WATER
 INFILTRATION REQUIREMENTS ARE NEEDED.
  
 CECO DOOR PRODUCTS IMPERIAL STEEL DOOR
 IS NOT APPROVED FOR USE WHERE WATER
 INFILTRATION REQUIREMENTS ARE NEEDED.
  
 OVERHEAD DOOR 16FT ROLLING INSULATED
 STEEL DOOR APPEARS COMPLIANT.SEE OTHER
 COMMENTS IN REGARDS TO DOR REVIEW AND
 STATE PRODUCT APPROVAL.
  
 PITTSBURGH CORNING GLASS BLOCK IS NOT
 COMPLIANT FOR ?WORST CASE? DESIGN
 PRESSURES.
  
 10.)SEE FBC*106.3.5.1.1.INFORMATION
 SUCH AS MINIMUM BUILDING TYPE FBC602.1,
 FBC503, FULLY SPRINKLED OR UNSPRINKLED,
 OCCUPANCY FBC3, OCCUPANT LOAD FBC1004
 AND EGRESS REQUIREMENTS, LIFE SAFETY
 PLAN FBC10 ARE NOT ON THE PLAN.PLEASE
 PROVIDE ALL REQUIRED INFORMATION.CODE
 COMPLIANCE CANNOT BE DETERMINED DUE TO
 INSUFFICIENT INFORMATION.
  
 FBC11-4.1.2(9), ACCESSIBLE MEANS OF
 EGRESS SHALL BE PROVIDED IN THE SAME
 NUMBER AS REQUIRED FOR EXITS BY LOCAL
 BUILDING/LIFE SAFETY REGULATIONS.ONLY
 TWO ACCESSIBLE MEANS OF EGRESS SHOWN;
 DOOR 7 SHOWS A STEP.THE OTHER TWO
 MEANS OF EGRESS DOES NOT COMPLY WITH
 FBC1005.1 (LOSS OF DOOR 1).
  
 11.)THE BOUNDARY SURVEY PREPARED BY
 WALLACE SURVEYORS IS TO BE SIGNED AND
 SEALED.
  
 12.)S-002, 03200, GENERAL NOTES, NOTE
 2 REFERS TO ACI318-95, FBC35.03300
 REFERS TO ACI301-96; 03200 REFERS TO
 ACI301-99.PLEASE REVIEW ALL
 REFERENCES.
  
 S-001 REFERS TO ACI347R-94 AND ASCE7-98.
 S-002 REFERS TO ACI315-94 AND
 ACI439-3R-83.REVISE IN ACCORDANCE WITH
 FBC35 AND CHECK ALL REFERENCES.
  
 13.)ADDRESSED.
  
 14.)FOR THE ONE HOUR WALL A2.0,
 PROVIDE EITHER AN APPROVED ASSEMBLY
 LISTING OR SHOW CALCULATED FIRE
 RESISTANCE FBC7.PROVIDE AN ASSEMBLY
 LISTING AND DETAIL FOR THE TOP OF THE
 WALL WHERE THE WALL MEETS THE DECK.
  
 THE WRITTEN DESCRIPTION ON A2.0
 CONFLICTS WITH THE DETAIL ON A2.2 AND
 CONFLICTS WITH THE UL ASSEMBLY
 REFERENCED.SEE ALSO UL U466 AS THE
 DETAIL YOU PROVIDED ON A2.2 MORE CLOSELY
 RESEMBLES THAT ASSEMBLY.DETAILS ARE TO
 BE CONSISTENT AND TO MEET THE
 SPECIFICATIONS OF THE ASSEMBLY YOU WISH
 TO USE.
  
 SHOW FIRE RESISTANCE OF THE ROOF DECK.
 THIS IS REQUIRED FOR THE UL HW DETAIL
 YOU SPECIFY AS WELL AS SHOWING
 COMPLIANCE WITH FBC708.4, CONTINUITY.
  
 15.)PROVIDE A GUARD DETAIL WITH
 INCLUDING DESIGN STRENGTH FBC1607.7,
 FBC1012.INCLUDE ALL DIMENSIONS.
  
 SHOW OPENING MAXIMUM DIMENSION
 FBC1012.3.ADD THE CONCENTRATED LOAD
 REQUIREMENT OF FBC1607.7.1.1 TO THE
 DESIGN SPECIFICATION.
  
 16-22.) ADDRESSED.
  
 23.)SHOW ACCESSIBLE SALES COUNTER,
 FBC11-7.2.
  
 PROVIDE DESIGN CRITERIA.REFERRING TO A
 CODE NUMBER IS NOT SUFFICIENT.
  
 NEW COMMENTS:
  
 24.)S-001 STRUCTURAL LOADING REFERS TO
 ASCE7-98; SHOULD BE ASCE7-02 FBC35.
  
 25.)THE ENERGY CALCS, CIVILS, AND
 ARCHITECTURALS CONFLICT AS TO THE
 BUILDING SIZE.NOTE THAT IMPACT FEE
 ASSESSMENT REVISION MAY BE REQUIRED WHEN
 THE ACTUAL BUILDING SIZE IS DETERMINED.
  
 26.)THE ENERGY CALCS REFER TO THE
 WRONG JURISDICTION.THE JURISDICTION
 NUMBER FOR THE CITY OF WEST PALM BEACH
 IS 604700, FBC APPENDIX 13A.INCLUDE
 ALL PERTINENT INFORMATION; OWNER, PERMIT
 NUMBER.
  
 27.)NOTHING ON THE SHEET 5 OF THE
 ENERGY CALCS IS MARKED AS BEING CHECKED.
 THIS IS REQUIRED TO SHOW CODE COMPLIANCE
 FBC13-103.1.1.1.
  
 28.)SOME ITEMS WERE NOT ENTERED FOR
 THE ENERGY CALCS; FOR INSTANCE, WATER
 HEATING SYSTEMS.INCLUDE ALL REQUIRED
 INFORMATION FBC13-103.
  
 29.)BE ADVISED THAT I ?SPOT CHECK? THE
 ENERGY CALCS.THE ABOVE CORRECTIONS MAY
 NOT INCLUDE ALL ITEMS.CONFIRM THAT ALL
 INFORMATION ON THE ENERGY CALC IS
 CORRECT PRIOR TO RESUBMITTAL.
  
 30.)ENERGY CALCS REQUIRED FOR THE
 FUTURE TENANT SPACE, FBC13-101.1.6.
  
 31.)SEPARATE PERMIT REQUIRED FOR THE
 DUMPSTER ENCLOSURE.PROVIDE A COMPLETED
 APPLICATION.
  
 32.)DOOR 17, SHOW MANEUVERING
 CLEARANCE, PULL SIDE FBC11-4.13, FBC
 FIGURE 25.
  
 33.)PARKING IS TO COMPLY WITH CITY OF
 WEST PALM BEACH STANDARD, SEE ATTACHED.
  
 34.)THE LANDSCAPE SHEETS PREPARED BY
 THE LANDSCAPE ARCHITECT ARE TO BE DATED
 AS WELL AS SIGNED AND SEALED, FS481.321.
  
 35.)S103, CLARIFY AS TO WHY TWO OF THE
 CORNERS ARE ZONE 2 RATHER THAN ZONE 3.
 FBC16.
  
 36.)E0.0 GENERAL NOTES REFERS TO THE
 WRONG BUILDING CODE, FBC2001 RATHER THAN
 FBC2004.
  
 37.)PROVIDE A FIRE SPRINKLER PLAN
 FBC*106.3.5.1.1(5).
  
  


Account Summary | Usage Policy | Privacy Policy