| 2006-03-24 00:00:00 | ****CORRECTIONS**** |
| | ****SECOND REVIEW (FIRST PERMIT |
| | REVIEW)**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | FROM PREVIOUS REVIEW, NUMBERING |
| | REMAINING THE SAME.ITEMS IN CAPITAL |
| | LETTERS ARE COMMENTS FROM THE SECOND |
| | REVIEW, WITH THE EXCEPTION OF THE LAST |
| | ITEMS WHICH ARE NEW COMMENTS. |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | THIS HAS BEEN DONE.PLEASE KEEP THE |
| | STAMPED SHEET AND THE RECEIPT IN THE |
| | PACKAGE WHEN RESUBMITTING. |
| | |
| | 3.)ADDRESSED. |
| | |
| | 4.-5.)ADDRESSED. |
| | |
| | 6.)THREE SETS OF PLANS AND ALL |
| | DOCUMENTS REQUIRED; RESIDENT INSPECTOR |
| | REQUIRED, FBC*109.3.7.PLEASE CONTACT |
| | HAROLD PISKURA, 561-805-6711. |
| | |
| | NOT ADDRESSED; ONLY TWO COPIES SUBMITTED |
| | ALTHOUGH THE RESPONSE LETTER STATES THAT |
| | THREE WERE SUBMITTED. |
| | |
| | THE RESPONSE THAT THIS WILL BE DONE |
| | PRIOR TO CONSTRUCTION IS ACKNOWLEDGED. |
| | NOTE THAT THIS IS REQUIRED PRIOR TO |
| | PERMIT ISSUANCE.TO AVOID FURTHER |
| | DELAYS, CONTACT HAROLD PISKURA AS |
| | REQUESTED.THE PRECONSTRUCTION MEETING |
| | AND INSPECTION PLAN APPROVED BY THE CITY |
| | ARE REQUIRED PRIOR TO PERMIT ISSUANCE. |
| | |
| | 7.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALCS, FBC13-103.1. |
| | |
| | THIS WAS SIGNED.HOWEVER, SEE OTHER |
| | CORRECTIONS REGARDING ENERGY CALCS.IF |
| | NEW ENERGY CALCS ARE PRODUCED PLEASE |
| | SIGN THE NEW CALCS.THREE COPIES ARE |
| | REQUIRED. |
| | |
| | 8.)ADDRESSED. |
| | |
| | 9.)SUBMIT PRODUCT APPROVALS, FAC9B72: |
| | |
| | ROOF |
| | STOREFRONT SYSTEM |
| | HOLLOW METAL DOOR |
| | ROLL UP DOOR |
| | GLASS BLOCK |
| | |
| | IF THE PRODUCTS SELECTED DO NOT MEET |
| | WORST CASE WIND PRESSURES AS SPECIFIED |
| | ON S-501, SUBMIT A SCHEDULE SPECIFYING |
| | PRESSURES FOR EACH OPENING. |
| | |
| | FOR THE ROOF PRODUCT APPROVAL, INDICATE |
| | WHICH APPROVED ASSEMBLY YOU ARE USING. |
| | SEE S-103 FOR ROOF PRESSURES. |
| | |
| | THREE COPIES OF ALL DOCUMENTS REQUIRED. |
| | ONLY TWO WERE SUBMITTED. |
| | |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVALS |
| | REQUIRED IN ADDITION TO THE NOAS |
| | PROVIDED, WWW.FLORIDABUILDING.ORG. |
| | PLEASE ADVISE IF IT IS NOT AVAILABLE FOR |
| | ANY OF THE PRODUCTS. |
| | |
| | PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| | DESIGNER OF RECORD FBC*106.3.3. |
| | |
| | SEE ABOVE REQUEST IN REGARDS TO THE WIND |
| | PRESSURES.PROVIDE THE DESIGN PRESSURES |
| | FOR EACH OPENING ON THE ELEVATIONS |
| | SHOWN.THE STOREFRONT SYSTEM, AS WELL |
| | AS OTHER PRODUCTS SUBMITTED, ARE NOT |
| | COMPLIANT FOR ?WORST CASE?.WORST CASE |
| | IS 10SF ZONE 5, +50.1/-66.8.SEVERAL OF |
| | THE PRODUCTS ARE NOT COMPLIANT. |
| | |
| | FOR THE GAF BUILT UP ROOF, THE |
| | ARCHITECT?S RESPONSE LETTER THAT YOU ARE |
| | USING SYSTEM B2 IS ACKNOWLEDGED. |
| | |
| | THE KAWNEER COMPANY SERIES 350-MS DOORS |
| | ARE NOT TO BE USED WHERE WATER |
| | INFILTRATION REQUIREMENT IS NEEDED. |
| | ADDRESS.IF YOU ARE GOING TO USE THIS |
| | DOOR, WRITE THE DOOR NUMBER DIRECTLY ON |
| | THE PRODUCT APPROVAL PRIOR TO REVIEW BY |
| | DESIGNER OF RECORD.DOR IS TO NOTE THAT |
| | THIS HAS BEEN ADDRESSED. |
| | |
| | YKK AP AMERICA YHS-50 DOOR, INDICATE ON |
| | SHEET 2 OF 6 OF THE PRODUCT APPROVAL |
| | WHICH CONFIGURATION AND SIZE YOU ARE |
| | INSTALLING.NOT ALL ARE COMPLIANT FOR |
| | WIND PRESSURES. |
| | |
| | YKK AP AMERICA 35H DOOR, INDICATE WHICH |
| | SPECIFIC OPTION YOU ARE INSTALLING.NOT |
| | ALL ARE COMPLIANT FOR WIND PRESSURES. |
| | |
| | STEELCRAFT MANUFACTURING STEEL DOOR IS |
| | NOT APPROVED FOR USE WHERE WATER |
| | INFILTRATION REQUIREMENTS ARE NEEDED. |
| | |
| | CECO DOOR PRODUCTS IMPERIAL STEEL DOOR |
| | IS NOT APPROVED FOR USE WHERE WATER |
| | INFILTRATION REQUIREMENTS ARE NEEDED. |
| | |
| | OVERHEAD DOOR 16FT ROLLING INSULATED |
| | STEEL DOOR APPEARS COMPLIANT.SEE OTHER |
| | COMMENTS IN REGARDS TO DOR REVIEW AND |
| | STATE PRODUCT APPROVAL. |
| | |
| | PITTSBURGH CORNING GLASS BLOCK IS NOT |
| | COMPLIANT FOR ?WORST CASE? DESIGN |
| | PRESSURES. |
| | |
| | 10.)SEE FBC*106.3.5.1.1.INFORMATION |
| | SUCH AS MINIMUM BUILDING TYPE FBC602.1, |
| | FBC503, FULLY SPRINKLED OR UNSPRINKLED, |
| | OCCUPANCY FBC3, OCCUPANT LOAD FBC1004 |
| | AND EGRESS REQUIREMENTS, LIFE SAFETY |
| | PLAN FBC10 ARE NOT ON THE PLAN.PLEASE |
| | PROVIDE ALL REQUIRED INFORMATION.CODE |
| | COMPLIANCE CANNOT BE DETERMINED DUE TO |
| | INSUFFICIENT INFORMATION. |
| | |
| | FBC11-4.1.2(9), ACCESSIBLE MEANS OF |
| | EGRESS SHALL BE PROVIDED IN THE SAME |
| | NUMBER AS REQUIRED FOR EXITS BY LOCAL |
| | BUILDING/LIFE SAFETY REGULATIONS.ONLY |
| | TWO ACCESSIBLE MEANS OF EGRESS SHOWN; |
| | DOOR 7 SHOWS A STEP.THE OTHER TWO |
| | MEANS OF EGRESS DOES NOT COMPLY WITH |
| | FBC1005.1 (LOSS OF DOOR 1). |
| | |
| | 11.)THE BOUNDARY SURVEY PREPARED BY |
| | WALLACE SURVEYORS IS TO BE SIGNED AND |
| | SEALED. |
| | |
| | 12.)S-002, 03200, GENERAL NOTES, NOTE |
| | 2 REFERS TO ACI318-95, FBC35.03300 |
| | REFERS TO ACI301-96; 03200 REFERS TO |
| | ACI301-99.PLEASE REVIEW ALL |
| | REFERENCES. |
| | |
| | S-001 REFERS TO ACI347R-94 AND ASCE7-98. |
| | S-002 REFERS TO ACI315-94 AND |
| | ACI439-3R-83.REVISE IN ACCORDANCE WITH |
| | FBC35 AND CHECK ALL REFERENCES. |
| | |
| | 13.)ADDRESSED. |
| | |
| | 14.)FOR THE ONE HOUR WALL A2.0, |
| | PROVIDE EITHER AN APPROVED ASSEMBLY |
| | LISTING OR SHOW CALCULATED FIRE |
| | RESISTANCE FBC7.PROVIDE AN ASSEMBLY |
| | LISTING AND DETAIL FOR THE TOP OF THE |
| | WALL WHERE THE WALL MEETS THE DECK. |
| | |
| | THE WRITTEN DESCRIPTION ON A2.0 |
| | CONFLICTS WITH THE DETAIL ON A2.2 AND |
| | CONFLICTS WITH THE UL ASSEMBLY |
| | REFERENCED.SEE ALSO UL U466 AS THE |
| | DETAIL YOU PROVIDED ON A2.2 MORE CLOSELY |
| | RESEMBLES THAT ASSEMBLY.DETAILS ARE TO |
| | BE CONSISTENT AND TO MEET THE |
| | SPECIFICATIONS OF THE ASSEMBLY YOU WISH |
| | TO USE. |
| | |
| | SHOW FIRE RESISTANCE OF THE ROOF DECK. |
| | THIS IS REQUIRED FOR THE UL HW DETAIL |
| | YOU SPECIFY AS WELL AS SHOWING |
| | COMPLIANCE WITH FBC708.4, CONTINUITY. |
| | |
| | 15.)PROVIDE A GUARD DETAIL WITH |
| | INCLUDING DESIGN STRENGTH FBC1607.7, |
| | FBC1012.INCLUDE ALL DIMENSIONS. |
| | |
| | SHOW OPENING MAXIMUM DIMENSION |
| | FBC1012.3.ADD THE CONCENTRATED LOAD |
| | REQUIREMENT OF FBC1607.7.1.1 TO THE |
| | DESIGN SPECIFICATION. |
| | |
| | 16-22.) ADDRESSED. |
| | |
| | 23.)SHOW ACCESSIBLE SALES COUNTER, |
| | FBC11-7.2. |
| | |
| | PROVIDE DESIGN CRITERIA.REFERRING TO A |
| | CODE NUMBER IS NOT SUFFICIENT. |
| | |
| | NEW COMMENTS: |
| | |
| | 24.)S-001 STRUCTURAL LOADING REFERS TO |
| | ASCE7-98; SHOULD BE ASCE7-02 FBC35. |
| | |
| | 25.)THE ENERGY CALCS, CIVILS, AND |
| | ARCHITECTURALS CONFLICT AS TO THE |
| | BUILDING SIZE.NOTE THAT IMPACT FEE |
| | ASSESSMENT REVISION MAY BE REQUIRED WHEN |
| | THE ACTUAL BUILDING SIZE IS DETERMINED. |
| | |
| | 26.)THE ENERGY CALCS REFER TO THE |
| | WRONG JURISDICTION.THE JURISDICTION |
| | NUMBER FOR THE CITY OF WEST PALM BEACH |
| | IS 604700, FBC APPENDIX 13A.INCLUDE |
| | ALL PERTINENT INFORMATION; OWNER, PERMIT |
| | NUMBER. |
| | |
| | 27.)NOTHING ON THE SHEET 5 OF THE |
| | ENERGY CALCS IS MARKED AS BEING CHECKED. |
| | THIS IS REQUIRED TO SHOW CODE COMPLIANCE |
| | FBC13-103.1.1.1. |
| | |
| | 28.)SOME ITEMS WERE NOT ENTERED FOR |
| | THE ENERGY CALCS; FOR INSTANCE, WATER |
| | HEATING SYSTEMS.INCLUDE ALL REQUIRED |
| | INFORMATION FBC13-103. |
| | |
| | 29.)BE ADVISED THAT I ?SPOT CHECK? THE |
| | ENERGY CALCS.THE ABOVE CORRECTIONS MAY |
| | NOT INCLUDE ALL ITEMS.CONFIRM THAT ALL |
| | INFORMATION ON THE ENERGY CALC IS |
| | CORRECT PRIOR TO RESUBMITTAL. |
| | |
| | 30.)ENERGY CALCS REQUIRED FOR THE |
| | FUTURE TENANT SPACE, FBC13-101.1.6. |
| | |
| | 31.)SEPARATE PERMIT REQUIRED FOR THE |
| | DUMPSTER ENCLOSURE.PROVIDE A COMPLETED |
| | APPLICATION. |
| | |
| | 32.)DOOR 17, SHOW MANEUVERING |
| | CLEARANCE, PULL SIDE FBC11-4.13, FBC |
| | FIGURE 25. |
| | |
| | 33.)PARKING IS TO COMPLY WITH CITY OF |
| | WEST PALM BEACH STANDARD, SEE ATTACHED. |
| | |
| | 34.)THE LANDSCAPE SHEETS PREPARED BY |
| | THE LANDSCAPE ARCHITECT ARE TO BE DATED |
| | AS WELL AS SIGNED AND SEALED, FS481.321. |
| | |
| | 35.)S103, CLARIFY AS TO WHY TWO OF THE |
| | CORNERS ARE ZONE 2 RATHER THAN ZONE 3. |
| | FBC16. |
| | |
| | 36.)E0.0 GENERAL NOTES REFERS TO THE |
| | WRONG BUILDING CODE, FBC2001 RATHER THAN |
| | FBC2004. |
| | |
| | 37.)PROVIDE A FIRE SPRINKLER PLAN |
| | FBC*106.3.5.1.1(5). |
| | |
| | |