Plan Review Notes
Plan Review Notes For Permit 05090770
Permit Number 05090770
Review Stop P
Sequence Number 1
Notes
Date Text
2005-11-14 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS ARE IN FOR FLAN REVIEW ONLY AT
 THIS TIME. PLANS SUBMITTED FOR PERMIT
 AFTER 10-01-05 SHALL BE DESIGNED FOR
 COMPLIANCE WITH FBC-2004.
 2. SHTS A1.0 THRU A7.4 IMPRESSION SEAL
 FOR ARCHITECT DOES NOT SHOW INFORMATION
 REQUIRED BY FAC 61G1-16.002(1) AND FS
 481.2055. PLEASE RESEAL SHEETS WITH A
 SEAL THAT IMPARTS INFORMATION REQUIRED.
 3. SHTS A1.0 THRU A7.4 AAC NUMBER IN
 TITLE BLOCK OF ARCHITECT DOES NOT SHOW
 UP ON DBPR WEBSITE IN SEARCH OF LICENSES
 PLEASE VERIFY NUMBER. (SEE ATTACHED
 SHEETS FROM DBPR WEBSITE, SHOWS LICENSE
 NUMBER FOR ARCHITECT).
 4. SHTS A2.0 AND A2.1 SHOW 5' TURNING
 AREA IN THE TOILET ROOM, NOT IN STALL.
 SECTION 11-4.22.3.
 5. SUBMIT CALCULATIONS FOR MINIMUM
 FIXTURE FACILITIES PER TABLES 1004.1.2
 AND 403.1. INDICATE SQUARE FOOTAGE FOR
 EACH OCCUPANCY AND OCCUPANCY LOAD FOR
 EACH AREA.
 6. SHT A2.1 ELEVATIONS 1 THRU 6 SHOW
 COMPLIANCE WITH:
 FOR W/C'S
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.6 DISPENSERS
 FOR URINALS
 A. FLUSH CONTROLS
 FOR LAVS
 A. 11-4.24.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
 7. SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.4 CONTROLS
 D. 11-4.15.5 CLEARANCES
 8. SHT A2.2 ELEVATION 7A, SHOW
 COMPLIANCE WITH:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE - SHALL
 BE FORWARD APPROACH AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK.
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
 9. SUBMIT CALCULATIONS FOR ROOF
 DRAINAGE. SHOW SQUARE FOOTAGE FOR THE
 ROOF AND SQUARE FOOTAGE DRAINED BY EACH
 DOWNSPOUT. SHOW 1/2 AREA OF ALL VERTICAL
 WALLS, INCLUDING PARAPETS IN
 CALCULATIONS. INDICATE THE GUTTER SIZE,
 AS WELL AS THE SLOPE OF THE GUTTER. SHOW
 THE HIGH & LOW POINTS OF THE GUTTER ON
 THE PLANS. INDICATE THE SIZE OF ALL
 DOWNSPOUTS.
 10. SHTS P1.0, P1.1, P1.2, & P1.3,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. FAC 61G15-23.002(2) AND FS
 471.025.
 11. SHT P1.2 GENERAL NOTES, AND KEYED
 NOTES #2 REFERENCE GAS SYSTEM. NO GAS
 SYSTEM LOCATED ON PLANS. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  