2005-12-03 00:00:00*****PLAN SUBMITTED FOR REVIEW ONLY*****
  
 1)MISSING INFORMATION ON TITLE BLOCK FOR
 ENGINEER OF REGORD PER FAC 61G15-23.002
  
 2)INDICATE LOCATION FOR SUPPLY AND
 RETURN DUCT SMOKE DETECTORS.DUCT
 DETECTORS SHALL BE CONNECTED TO BUILDING
 FIRE ALARM SYSTEM IF APPLICABLE OR BE
 PROVIDED WITH VISIBLE/AUDIBLE
 NOTIFICATION PER FBC,M 2004 606.4.1
  
 3)CONDENSATE DISPOSAL ON ROOF TO BE
 PIPED TO APPROVED ROOF DRAIN OR 6" RAIN
 LEADERS WHICH ARE SHOWN ON PLAN PROVIDED
 THE RAIN LEADER DISCHARGE LOCATION IS IN
 COMPLIANCE WITH FBC,M 2004 307.2.1
  
 4)AUXILIARY/SECONDARY DRAIN PROTECTION
 IS REQUIRED FOR ROOFTOP PACKAGE UNITS
 PER FBC,M 2004 307.2.3.THIS CAN BE
 ACCOMPLISHED VIA A WATER-LEVEL DETECTION
 DEVICE LOCATED IN EACH UNIT'S PRIMARY
 DRAIN PAN.
  
 ANY QUESTIONS PLEASE CALL RONALD J.
 REGUEIRO AT 561-805-6734 OR PATTY KRAUS
 AT 561.805.6719