| Plan Review Notes For Permit 05090770 |
| Permit Number |
05090770 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-03 00:00:00 | *****PLAN SUBMITTED FOR REVIEW ONLY***** | | | | | | 1)MISSING INFORMATION ON TITLE BLOCK FOR | | | ENGINEER OF REGORD PER FAC 61G15-23.002 | | | | | | 2)INDICATE LOCATION FOR SUPPLY AND | | | RETURN DUCT SMOKE DETECTORS.DUCT | | | DETECTORS SHALL BE CONNECTED TO BUILDING | | | FIRE ALARM SYSTEM IF APPLICABLE OR BE | | | PROVIDED WITH VISIBLE/AUDIBLE | | | NOTIFICATION PER FBC,M 2004 606.4.1 | | | | | | 3)CONDENSATE DISPOSAL ON ROOF TO BE | | | PIPED TO APPROVED ROOF DRAIN OR 6" RAIN | | | LEADERS WHICH ARE SHOWN ON PLAN PROVIDED | | | THE RAIN LEADER DISCHARGE LOCATION IS IN | | | COMPLIANCE WITH FBC,M 2004 307.2.1 | | | | | | 4)AUXILIARY/SECONDARY DRAIN PROTECTION | | | IS REQUIRED FOR ROOFTOP PACKAGE UNITS | | | PER FBC,M 2004 307.2.3.THIS CAN BE | | | ACCOMPLISHED VIA A WATER-LEVEL DETECTION | | | DEVICE LOCATED IN EACH UNIT'S PRIMARY | | | DRAIN PAN. | | | | | | ANY QUESTIONS PLEASE CALL RONALD J. | | | REGUEIRO AT 561-805-6734 OR PATTY KRAUS | | | AT 561.805.6719 |
|