Plan Review Notes
Plan Review Notes For Permit 05090770
Permit Number 05090770
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-11-15 00:00:00******DENIED******
  
 PLAN REVIEW ONLY
  
 1) ALL ACCESS ROADS FOR EMERGENCY
 TRAFFIC ARE TO BE MAINTAINED AT MINIMUM
 CLEAR AND UNOBSTRUCTED WIDTH OF 20'.
  
 2) AN ADDRESS IS REQUIRED ON THE
 BUILDING AND SHALL BE A MINIMUM OF 6" IN
 HEIGHT AND CONTRASTING TO THE
 BACKGROUND. PLEASE PROVIDE ON ELEVATION
 SHEET.
  
 3) NFPA 101, 2003 EDITION TO BE
 REFERENCED AFTER JAN. 1, 2005.
  
 4) PLEASE SHOW LOCATION OF ALL HYDRANTS
 THAT ARE TO BE WET AND OPERATIONAL PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 5) PLEASE SUBMIT A LIFE SAFETY PLAN TO
 DETERMINE REQUIRED MEANS OF EGRESS WHEN
 SUBMITTING FOR PERMIT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722