| Date |
Text |
| 2005-10-11 00:00:00 | IN ELEC FOR REVIEW. |
| | GOLF SMITH |
| | |
| | ********* UNSAT *********** |
| | |
| | PLEASE KNOW, PLANS WERE ONLY SUBMITTED |
| | FOR "PLAN REVIEW" AND WERE NOT |
| | SUBMITTED FOR PERMIT. |
| | PLEASE SEE THE FOLLOWING COMMENTS. |
| | |
| | |
| | 1)NOTE: PLEASE SEE DUE TO PLANS BEING |
| | SUBMITTED FOR "PLAN REVIEW" ONLY, PLEASE |
| | BE AWARE AS OF OCT 1ST, 2005 THE NEW FBC |
| | 2004 HAS BEEN ADOPTED AND IS NOW IN |
| | EFFECT. |
| | PLEASE SEE PLANS REFERENCE 2001 FBC |
| | WHICH CAN NO LONGER BE USED FOR DESIGN |
| | AND USE FOR THIS PROJECT. |
| | PLEASE KNOW WHEN SUBMITTING FOR PERMIT A |
| | , NEW PERMIT NUMBER WILL BE REQUIRED TO |
| | BE GENERATED FOR PROCESSING AFTER OCT |
| | 1ST, 2005. |
| | PLEASE SEE WRONG CODE REFERENCED FOR |
| | LS101. NFPA-101 IS THE 2003 EDITION. |
| | PLEASE SEE OTHER COMMENTS FROM OTHER |
| | REVIEWERS WHICH WILL APPLY TO CODE |
| | CHANGE. |
| | |
| | 2)NOTE: PLEASE SEE MISSING INFORMATION |
| | ON TITLE BLOCKS FOR ALL ENGINEER'S OF |
| | RECORD AS REQUIRED UNDER FAC |
| | 61G15-23.002. |
| | PLEASE SEE M, E, P, PLANS ARE SIGNED, |
| | DATED AND SEALED BY ENGINEER'S, HOWEVER |
| | NO TITLE BLOCKS ARE SHOWN?? |
| | PLEASE ALSO SEE FS 471.023 IF APPLICABLE |
| | FOR CERTIFICATE OF AUTHORIZATION NUMBER. |
| | THIS IS REQUIRED OF ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 3)NOTE: PLEASE SUBMIT COMPLETE |
| | WIND-LOADING CALCULATIONS FOR |
| | SITE-LIGHTING POLES AND FIXTURES. |
| | PLEASE SUBMIT A DETAIL FOR POLE/FIXTURE |
| | AND FOUNDATION FOR POLE(S). |
| | PLEASE KNOW THE WIND LOADS ARE FER FBC |
| | 140 MPH. |
| | PLEASE KNOW THAT THE STRUCTUAL |
| | CALCULATIONS WILL BE REVIEWED BY THE |
| | BUILDING REVIEWER. |
| | |
| | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | IT IT NOTED THAT THE AIC RATINGS ARE |
| | SHOWN FOR MDP AND SUB PANELS, HOWEVER |
| | PLEASE INDICATE FOR MAIN DISCONNECTS. |
| | |
| | 5)NOTE: PLEASE SEE PANEL "LB" IS BEING |
| | FED FROM MDP WITH 100A OCPWITH 3/0'S?? |
| | PLEASE KNOW THIS IS OK AND MEETS CODE, |
| | HOWEVER IF SHOWN WITH 3/0'S THEN 3/0'S |
| | WILL BE REQUIRED TO BE INSTALLED. |
| | VERIFY OF 3/0S CONNECT INTO A 100A BRKR |
| | LUGS WITH OUT ANY ADAPTER(S). |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SEE PANEL "CR" WHICH |
| | INDICATES A 60A SUB FEED OCP FROM MDP, |
| | HOWEVER RISER NOTES SHOWS #10'S AWG? |
| | PLEASE SEE 240.310.16 FOR MIN AWG |
| | REQUIRED FOR 60A OCP. |
| | PLEASE ALSO SEE PANEL "CR" IS ALSO SHOWN |
| | AS A 20CIRCUIT 30A PANEL? PLEASE VERIFY |
| | BUS RATING, PANEL RATING ETC, AS THIS |
| | DOES NOT SEEM TO BE A COMMON PANEL. |
| | 215.5 |
| | |
| | 7)NOTE: PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS FOR REVIEW. PLEASE ALSO |
| | INDICATE ALL CONTINUOUS LOADS AND |
| | LARGEST MOTOR LOADS AT 125%. |
| | 220.3,220.10,220.13,220.11,215.3,230.42 |
| | ETC. |
| | |
| | 8)NOTE: PLEASE VERIFY LOCATION OF NEW |
| | PANEL T-1 WHICH IS BEING SHOWN IN |
| | "FUTURE TOILET RM" IN FUTURE TENANT |
| | SPACE. |
| | 240.24,215.5 |
| | |
| | 9)NOTE: PLEASE INDICATE ALL ROOF-TOP |
| | RECEPTS WHICH ARE SHOWN FOR RFTOP A/C |
| | EQUIPMENT AS GFI/GFI PROTECTED. |
| | 210.8B2 |
| | |
| | 10)NOTE: PLEASE SEE 210.62, 220.12 FOR |
| | MISSING "SHOW WINDOW" RECEPTS WHICH ARE |
| | AND WILL BE REQUIRED. |
| | |
| | 11)NOTE: PLEASE SEE PANEL SCHEDULE LA |
| | INDICATES NUMEROUS "SIGN CIRCUITS" FOR |
| | SIGNAGE, HOWEVER, 600.5 REQUIRES A MIN |
| | OF ONE CIRCUIT AT THE LOCATION OF THE |
| | FRONT DOOR OR IMMEDIATE VICINITY THERTO. |
| | PLEASE CALRIFY WHERE THESE SIGN CIRCUITS |
| | ARE ON PLANS. |
| | |
| | 12)NOTE: PLEASE SEE ELECTRICLA PLANS DO |
| | NOT INDICATE ANY SINKS IN BREAK RM, |
| | HOWEVER ALL RECEPTS LOCATED WITHIN 6' OF |
| | A SINK SHALL BE GFI/GFI |
| | PROTECTED.210.8B3, PLEASE CALL TO GO |
| | OVER CHANGES TO THE 2002 NEC. |
| | |
| | 13)NOTE: PLEASE SEE NEC WHICH REQUIRES |
| | THE GROUNDING ELECTRODE TO BE |
| | CONTINUOUS, WHICH WOULD REQUIRE THE 3/0 |
| | TO GROUND ROD ALSO. SHOWN AS #6.250.50 |
| | |
| | ** PLEASE SEE NOTE NUMBER ONE, PLANS DI |
| | NOT COME IN FOR PERMIT UNDER THE 2001 |
| | FBC. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | EELCTRICAL PLANS. |
| | |
| | ** PLEASE COMPLETELY REMOVE ANY |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SUBMIT ONE COMPLETE SET OF ALL |
| | OLD/VOIDED SHEETS FOR REFERENCE ONLY. |
| | THESE SHALL BE SEPARATE FROM COMPLETE |
| | SETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |