Plan Review Notes
Plan Review Notes For Permit 05090770
Permit Number 05090770
Review Stop E
Sequence Number 1
Notes
Date Text
2005-10-11 00:00:00IN ELEC FOR REVIEW.
 GOLF SMITH
  
 ********* UNSAT ***********
  
 PLEASE KNOW, PLANS WERE ONLY SUBMITTED
 FOR "PLAN REVIEW" AND WERE NOT
 SUBMITTED FOR PERMIT.
 PLEASE SEE THE FOLLOWING COMMENTS.
  
  
 1)NOTE: PLEASE SEE DUE TO PLANS BEING
 SUBMITTED FOR "PLAN REVIEW" ONLY, PLEASE
 BE AWARE AS OF OCT 1ST, 2005 THE NEW FBC
 2004 HAS BEEN ADOPTED AND IS NOW IN
 EFFECT.
 PLEASE SEE PLANS REFERENCE 2001 FBC
 WHICH CAN NO LONGER BE USED FOR DESIGN
 AND USE FOR THIS PROJECT.
 PLEASE KNOW WHEN SUBMITTING FOR PERMIT A
 , NEW PERMIT NUMBER WILL BE REQUIRED TO
 BE GENERATED FOR PROCESSING AFTER OCT
 1ST, 2005.
 PLEASE SEE WRONG CODE REFERENCED FOR
 LS101. NFPA-101 IS THE 2003 EDITION.
 PLEASE SEE OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH WILL APPLY TO CODE
 CHANGE.
  
 2)NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS FOR ALL ENGINEER'S OF
 RECORD AS REQUIRED UNDER FAC
 61G15-23.002.
 PLEASE SEE M, E, P, PLANS ARE SIGNED,
 DATED AND SEALED BY ENGINEER'S, HOWEVER
 NO TITLE BLOCKS ARE SHOWN??
 PLEASE ALSO SEE FS 471.023 IF APPLICABLE
 FOR CERTIFICATE OF AUTHORIZATION NUMBER.
 THIS IS REQUIRED OF ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3)NOTE: PLEASE SUBMIT COMPLETE
 WIND-LOADING CALCULATIONS FOR
 SITE-LIGHTING POLES AND FIXTURES.
 PLEASE SUBMIT A DETAIL FOR POLE/FIXTURE
 AND FOUNDATION FOR POLE(S).
 PLEASE KNOW THE WIND LOADS ARE FER FBC
 140 MPH.
 PLEASE KNOW THAT THE STRUCTUAL
 CALCULATIONS WILL BE REVIEWED BY THE
 BUILDING REVIEWER.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 IT IT NOTED THAT THE AIC RATINGS ARE
 SHOWN FOR MDP AND SUB PANELS, HOWEVER
 PLEASE INDICATE FOR MAIN DISCONNECTS.
  
 5)NOTE: PLEASE SEE PANEL "LB" IS BEING
 FED FROM MDP WITH 100A OCPWITH 3/0'S??
 PLEASE KNOW THIS IS OK AND MEETS CODE,
 HOWEVER IF SHOWN WITH 3/0'S THEN 3/0'S
 WILL BE REQUIRED TO BE INSTALLED.
 VERIFY OF 3/0S CONNECT INTO A 100A BRKR
 LUGS WITH OUT ANY ADAPTER(S).
 215.5
  
 6)NOTE: PLEASE SEE PANEL "CR" WHICH
 INDICATES A 60A SUB FEED OCP FROM MDP,
 HOWEVER RISER NOTES SHOWS #10'S AWG?
 PLEASE SEE 240.310.16 FOR MIN AWG
 REQUIRED FOR 60A OCP.
 PLEASE ALSO SEE PANEL "CR" IS ALSO SHOWN
 AS A 20CIRCUIT 30A PANEL? PLEASE VERIFY
 BUS RATING, PANEL RATING ETC, AS THIS
 DOES NOT SEEM TO BE A COMMON PANEL.
 215.5
  
 7)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR REVIEW. PLEASE ALSO
 INDICATE ALL CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS AT 125%.
 220.3,220.10,220.13,220.11,215.3,230.42
 ETC.
  
 8)NOTE: PLEASE VERIFY LOCATION OF NEW
 PANEL T-1 WHICH IS BEING SHOWN IN
 "FUTURE TOILET RM" IN FUTURE TENANT
 SPACE.
 240.24,215.5
  
 9)NOTE: PLEASE INDICATE ALL ROOF-TOP
 RECEPTS WHICH ARE SHOWN FOR RFTOP A/C
 EQUIPMENT AS GFI/GFI PROTECTED.
 210.8B2
  
 10)NOTE: PLEASE SEE 210.62, 220.12 FOR
 MISSING "SHOW WINDOW" RECEPTS WHICH ARE
 AND WILL BE REQUIRED.
  
 11)NOTE: PLEASE SEE PANEL SCHEDULE LA
 INDICATES NUMEROUS "SIGN CIRCUITS" FOR
 SIGNAGE, HOWEVER, 600.5 REQUIRES A MIN
 OF ONE CIRCUIT AT THE LOCATION OF THE
 FRONT DOOR OR IMMEDIATE VICINITY THERTO.
 PLEASE CALRIFY WHERE THESE SIGN CIRCUITS
 ARE ON PLANS.
  
 12)NOTE: PLEASE SEE ELECTRICLA PLANS DO
 NOT INDICATE ANY SINKS IN BREAK RM,
 HOWEVER ALL RECEPTS LOCATED WITHIN 6' OF
 A SINK SHALL BE GFI/GFI
 PROTECTED.210.8B3, PLEASE CALL TO GO
 OVER CHANGES TO THE 2002 NEC.
  
 13)NOTE: PLEASE SEE NEC WHICH REQUIRES
 THE GROUNDING ELECTRODE TO BE
 CONTINUOUS, WHICH WOULD REQUIRE THE 3/0
 TO GROUND ROD ALSO. SHOWN AS #6.250.50
  
 ** PLEASE SEE NOTE NUMBER ONE, PLANS DI
 NOT COME IN FOR PERMIT UNDER THE 2001
 FBC.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 EELCTRICAL PLANS.
  
 ** PLEASE COMPLETELY REMOVE ANY
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE COMPLETE SET OF ALL
 OLD/VOIDED SHEETS FOR REFERENCE ONLY.
 THESE SHALL BE SEPARATE FROM COMPLETE
 SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  