| 2005-11-09 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | 3.)A PERMIT APPLICATION MUST BE |
| | SUBMITTED PRIOR TO PERMIT ISSUANCE. |
| | THIS IS A PLAN CHECK ONLY. |
| | |
| | 4.)PERMITS APPLIED FOR ON OR AFTER |
| | OCTOBER 1, 2005 ARE TO BE DESIGNED UNDER |
| | FBC2004.SOME PAGES REFER TO FBC2001, |
| | INCLUDING S-001, S-103. CHECK ALL |
| | SHEETS. ARCHITECT AND ENGINEER BOTH ARE |
| | TO INDICATE THAT THE PLANS HAVE BEEN |
| | DESIGNED TO FBC2004. |
| | |
| | 5.)SOME OF THE SHEETS WERE BOUND |
| | UPSIDE DOWN.THIS DELAYS PLAN REVIEW. |
| | PLEASE SUBMIT PROPERLY. |
| | |
| | 6.)THREE SETS OF PLANS AND ALL |
| | DOCUMENTS REQUIRED; RESIDENT INSPECTOR |
| | REQUIRED, FBC*109.3.7.PLEASE CONTACT |
| | HAROLD PISKURA, 561-805-6711. |
| | |
| | 7.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALCS, FBC13-103.1. |
| | |
| | 8.)FOR THE ARCHITECT TITLE BLOCK, THE |
| | PRINTED NAME OF THE PERSON SEALING THE |
| | DOCUMENT IS TO BE ON THE PLAN, |
| | FAC61G1-16.003, 004. |
| | |
| | 9.)SUBMIT PRODUCT APPROVALS, FAC9B72: |
| | |
| | ROOF |
| | STOREFRONT SYSTEM |
| | HOLLOW METAL DOOR |
| | ROLL UP DOOR |
| | |
| | IF THE PRODUCTS SELECTED DO NOT MEET |
| | WORST CASE WIND PRESSURES AS SPECIFIED |
| | ON S-501, SUBMIT A SCHEDULE SPECIFYING |
| | PRESSURES FOR EACH OPENING. |
| | |
| | FOR THE ROOF PRODUCT APPROVAL, INDICATE |
| | WHICH APPROVED ASSEMBLY YOU ARE USING. |
| | SEE S-103 FOR ROOF PRESSURES. |
| | |
| | 10.)SEE FBC*106.3.5.1.1.INFORMATION |
| | SUCH AS MINIMUM BUILDING TYPE FBC602.1, |
| | FBC503, FULLY SPRINKLED OR UNSPRINKLED, |
| | OCCUPANCY FBC3, OCCUPANT LOAD FBC1004 |
| | AND EGRESS REQUIREMENTS, LIFE SAFETY |
| | PLAN FBC10 ARE NOT ON THE PLAN.PLEASE |
| | PROVIDE ALL REQUIRED INFORMATION.CODE |
| | COMPLIANCE CANNOT BE DETERMINED DUE TO |
| | INSUFFICIENT INFORMATION. |
| | |
| | 11.)THE BOUNDARY SURVEY PREPARED BY |
| | WALLACE SURVEYORS IS TO BE SIGNED AND |
| | SEALED. |
| | |
| | 12.)S-002, 03200, GENERAL NOTES, NOTE |
| | 2 REFERS TO ACI318-95, FBC35.03300 |
| | REFERS TO ACI301-96; 03200 REFERS TO |
| | ACI301-99.PLEASE REVIEW ALL |
| | REFERENCES. |
| | |
| | 13.)11-201 STATES THAT THE RETAINING |
| | WALL WILL BE DESIGNED BY THE CIVIL |
| | ENGINEER.PROVIDE A DETAIL. |
| | |
| | 14.)FOR THE ONE HOUR WALL A2.0, |
| | PROVIDE EITHER AN APPROVED ASSEMBLY |
| | LISTING OR SHOW CALCULATED FIRE |
| | RESISTANCE FBC7.PROVIDE AN ASSEMBLY |
| | LISTING AND DETAIL FOR THE TOP OF THE |
| | WALL WHERE THE WALL MEETS THE DECK. |
| | |
| | 15.)PROVIDE A GUARD DETAIL WITH |
| | INCLUDING DESIGN STRENGTH FBC1607.7, |
| | FBC1012.INCLUDE ALL DIMENSIONS. |
| | |
| | 16.)PROVIDE A DETAIL FOR THE RAMP |
| | HANDRAILS, FBC1010, FBC11-4.8, |
| | FBC11-4.26. |
| | |
| | 17.)LANDING AT THE BOTTOM OF A RAMP |
| | SHALL BE NOT LESS THAN 72IN,FBC11-4.8.4. |
| | |
| | 18.)PROVIDE DETAILS FOR THE HANDRAILS, |
| | FBC11-4.26.SHOW THE EXTENSION AT THE |
| | BOTTOM, SEE FBC11 FIGURE 19(C). |
| | |
| | 19.)IS THE DETAIL FOR THE GOLFSMITH |
| | ENTRANCE TO BE USED FOR THE FUTURE |
| | TENANT ENTRANCE?A RAMP IS SHOWN ON THE |
| | CROSS SECTION DETAIL 1-301, SHEET S-301, |
| | BUT NOT ON THE CIVILS, ARCHITECTURALS, |
| | OR OTHER STRUCTURAL SHEETS.THIS |
| | ENTRANCE IS TO BE ACCESSIBLE; CANNOT |
| | HAVE A .25 FOOT STEP AS SHOWN ON THE |
| | CIVILS. |
| | |
| | 20.)THE SECTION INDICATED FOR THE |
| | ENTRANCE TO GOLFSMITH, 11-201, IS THE |
| | DETAIL FOR THE DUMPSTER ENCLOSURE. |
| | |
| | 21.)SEE A3.0 AND A2.3.THE ELEVATION |
| | FOR THE ENTRANCE CONFLICTS WITH THE PLAN |
| | VIEW (PLANTER NOT SHOWN ON THE |
| | ELEVATION). |
| | |
| | 22.)THE WALKWAY BETWEEN THE BUILDING |
| | AND THE LOADING AREA APPEARS TO SLOPE. |
| | SPECIFY THE DEGREE OF SLOPE.IF THIS |
| | AREA IS NOT SLOPED, HOW DOES IT |
| | TRANSITION FROM THE 18' FFE TO THE |
| | SIDEWALK IN THE FRONT? |
| | |
| | 23.)SHOW ACCESSIBLE SALES COUNTER, |
| | FBC11-7.2. |