2005-11-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)A PERMIT APPLICATION MUST BE
 SUBMITTED PRIOR TO PERMIT ISSUANCE.
 THIS IS A PLAN CHECK ONLY.
  
 4.)PERMITS APPLIED FOR ON OR AFTER
 OCTOBER 1, 2005 ARE TO BE DESIGNED UNDER
 FBC2004.SOME PAGES REFER TO FBC2001,
 INCLUDING S-001, S-103. CHECK ALL
 SHEETS. ARCHITECT AND ENGINEER BOTH ARE
 TO INDICATE THAT THE PLANS HAVE BEEN
 DESIGNED TO FBC2004.
  
 5.)SOME OF THE SHEETS WERE BOUND
 UPSIDE DOWN.THIS DELAYS PLAN REVIEW.
 PLEASE SUBMIT PROPERLY.
  
 6.)THREE SETS OF PLANS AND ALL
 DOCUMENTS REQUIRED; RESIDENT INSPECTOR
 REQUIRED, FBC*109.3.7.PLEASE CONTACT
 HAROLD PISKURA, 561-805-6711.
  
 7.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS, FBC13-103.1.
  
 8.)FOR THE ARCHITECT TITLE BLOCK, THE
 PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT IS TO BE ON THE PLAN,
 FAC61G1-16.003, 004.
  
 9.)SUBMIT PRODUCT APPROVALS, FAC9B72:
  
 ROOF
 STOREFRONT SYSTEM
 HOLLOW METAL DOOR
 ROLL UP DOOR
  
 IF THE PRODUCTS SELECTED DO NOT MEET
 WORST CASE WIND PRESSURES AS SPECIFIED
 ON S-501, SUBMIT A SCHEDULE SPECIFYING
 PRESSURES FOR EACH OPENING.
  
 FOR THE ROOF PRODUCT APPROVAL, INDICATE
 WHICH APPROVED ASSEMBLY YOU ARE USING.
 SEE S-103 FOR ROOF PRESSURES.
  
 10.)SEE FBC*106.3.5.1.1.INFORMATION
 SUCH AS MINIMUM BUILDING TYPE FBC602.1,
 FBC503, FULLY SPRINKLED OR UNSPRINKLED,
 OCCUPANCY FBC3, OCCUPANT LOAD FBC1004
 AND EGRESS REQUIREMENTS, LIFE SAFETY
 PLAN FBC10 ARE NOT ON THE PLAN.PLEASE
 PROVIDE ALL REQUIRED INFORMATION.CODE
 COMPLIANCE CANNOT BE DETERMINED DUE TO
 INSUFFICIENT INFORMATION.
  
 11.)THE BOUNDARY SURVEY PREPARED BY
 WALLACE SURVEYORS IS TO BE SIGNED AND
 SEALED.
  
 12.)S-002, 03200, GENERAL NOTES, NOTE
 2 REFERS TO ACI318-95, FBC35.03300
 REFERS TO ACI301-96; 03200 REFERS TO
 ACI301-99.PLEASE REVIEW ALL
 REFERENCES.
  
 13.)11-201 STATES THAT THE RETAINING
 WALL WILL BE DESIGNED BY THE CIVIL
 ENGINEER.PROVIDE A DETAIL.
  
 14.)FOR THE ONE HOUR WALL A2.0,
 PROVIDE EITHER AN APPROVED ASSEMBLY
 LISTING OR SHOW CALCULATED FIRE
 RESISTANCE FBC7.PROVIDE AN ASSEMBLY
 LISTING AND DETAIL FOR THE TOP OF THE
 WALL WHERE THE WALL MEETS THE DECK.
  
 15.)PROVIDE A GUARD DETAIL WITH
 INCLUDING DESIGN STRENGTH FBC1607.7,
 FBC1012.INCLUDE ALL DIMENSIONS.
  
 16.)PROVIDE A DETAIL FOR THE RAMP
 HANDRAILS, FBC1010, FBC11-4.8,
 FBC11-4.26.
  
 17.)LANDING AT THE BOTTOM OF A RAMP
 SHALL BE NOT LESS THAN 72IN,FBC11-4.8.4.
  
 18.)PROVIDE DETAILS FOR THE HANDRAILS,
 FBC11-4.26.SHOW THE EXTENSION AT THE
 BOTTOM, SEE FBC11 FIGURE 19(C).
  
 19.)IS THE DETAIL FOR THE GOLFSMITH
 ENTRANCE TO BE USED FOR THE FUTURE
 TENANT ENTRANCE?A RAMP IS SHOWN ON THE
 CROSS SECTION DETAIL 1-301, SHEET S-301,
 BUT NOT ON THE CIVILS, ARCHITECTURALS,
 OR OTHER STRUCTURAL SHEETS.THIS
 ENTRANCE IS TO BE ACCESSIBLE; CANNOT
 HAVE A .25 FOOT STEP AS SHOWN ON THE
 CIVILS.
  
 20.)THE SECTION INDICATED FOR THE
 ENTRANCE TO GOLFSMITH, 11-201, IS THE
 DETAIL FOR THE DUMPSTER ENCLOSURE.
  
 21.)SEE A3.0 AND A2.3.THE ELEVATION
 FOR THE ENTRANCE CONFLICTS WITH THE PLAN
 VIEW (PLANTER NOT SHOWN ON THE
 ELEVATION).
  
 22.)THE WALKWAY BETWEEN THE BUILDING
 AND THE LOADING AREA APPEARS TO SLOPE.
 SPECIFY THE DEGREE OF SLOPE.IF THIS
 AREA IS NOT SLOPED, HOW DOES IT
 TRANSITION FROM THE 18' FFE TO THE
 SIDEWALK IN THE FRONT?
  
 23.)SHOW ACCESSIBLE SALES COUNTER,
 FBC11-7.2.