| 2005-11-07 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT A SITE PLAN INDICATING | | | THE EXISTING SERVICE EQUIPMENT AS WELL | | | AS THE GENERATOR EQUIPMENT SO THAT | | | COMPLIANCE WITH ARTICLES 225.31 THROUGH | | | 225.37 INCLUSIVE, MAY BE DETERMINED. | | | | | | NOTE THAT PER THE ARTICLES SITED ABOVE, | | | THE DISCONNECTING MEANS PER 225.31 MUST | | | BE SERVICE RATED PER 225.36.THE | | | GENERATOR DISCONNECTING MEANS (IN THE | | | UNIT) IS NOT ACCEPTABLE FOR THIS | | | PURPOSE. | | | | | | 2} SEE ARTICLE 445.13 FFOR FEEDER | | | CONDUCTOR SIZE, 115% OF NAMEPLATE. | | | | | | 3} PER RISER SUBMITTED THERE IS NO | | | UTILITY POWER TO THE ATS. | | | | | | 5} THE PERSON RESPONSIBLE FOR THE | | | DRAWING MUST PRINT AND SIGN THEIR NAME | | | ON SAME. 104.2.1 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|