2005-09-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE PRIME MOVER (FUEL
 SOURCE).
  
 2} PLEASE SUBMIT A SITE PLAN INDICATING
 THE EXISTING SERVICE EQUIPMENT AS WELL
 AS THE GENERATOR EQUIPMENT SO THAT
 COMPLIANCE WITH ARTICLES 225.31 THROUGH
 225.37 INCLUSIVE, MAY BE DETERMINED.
  
 NOTE THAT PER THE ARTICLES SITED ABOVE,
 THE DISCONNECTING MEANS PER 225.31 MUST
 BE SERVICE RATED PER 225.36.THE
 GENERATOR DISCONNECTING MEANS (IN THE
 UNIT) IS NOT ACCEPTABLE FOR THIS
 PURPOSE.
  
 3} PLEASE SUBMIT A LOAD CALCULATION AND
 PANEL SCHEDULE FOR THE CIRCUITS TO BE
 CONNECTED TO THE GENERATOR. 215.5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  