| Plan Review Notes For Permit 05090758 |
| Permit Number |
05090758 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-26 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE INDICATE THE PRIME MOVER (FUEL | | | SOURCE). | | | | | | 2} PLEASE SUBMIT A SITE PLAN INDICATING | | | THE EXISTING SERVICE EQUIPMENT AS WELL | | | AS THE GENERATOR EQUIPMENT SO THAT | | | COMPLIANCE WITH ARTICLES 225.31 THROUGH | | | 225.37 INCLUSIVE, MAY BE DETERMINED. | | | | | | NOTE THAT PER THE ARTICLES SITED ABOVE, | | | THE DISCONNECTING MEANS PER 225.31 MUST | | | BE SERVICE RATED PER 225.36.THE | | | GENERATOR DISCONNECTING MEANS (IN THE | | | UNIT) IS NOT ACCEPTABLE FOR THIS | | | PURPOSE. | | | | | | 3} PLEASE SUBMIT A LOAD CALCULATION AND | | | PANEL SCHEDULE FOR THE CIRCUITS TO BE | | | CONNECTED TO THE GENERATOR. 215.5. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|