| Plan Review Notes For Permit 05090750 |
| Permit Number |
05090750 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-06 00:00:00 | ******DENIED****** | | | | | | 1) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL IF APPLICABLE. | | | | | | 2) PLEASE SHOW LOCATIONS OF ILLUMINATED | | | EXIT SIGNS AND EMERGENCY LIGHTING | | | FACILITIES. | | | | | | 3) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED AND SHALL BE MOUNTED AT | | | LOCATIONS TO SATISFY THE 75' TRAVEL | | | DISTANCE REQUIREMENT. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | (561) 805-6722 |
|